A 220 kV transformer tripping accident caused by heavy gas misoperation of oil-flow relay in on-load tap-changer (OLTC) is analyzed. Through the test and examination of the insulation resistance of reed switch in oil-flow relay and combined with the fault recording wave
the accident action logic is repeatedly deduced and analyzed. The root causes of the accident and a design defect of reed switch in oil-flow relay are found out
Analysis of An Accident Caused by Heavy Gas Misoperation of Oil-flow Relay
Modification for the Interface of Oil Evacuation and Nitrogen Injection Extinguishing Device in Old Type Transformer
Analysis on Open-phase Fault of 110 kV GIS Disconnector
On-site Comprehensive Diagnosis Method of Partial Discharge for Transformer Equipment Based on Ultrasonic Associated with Electromagnetic Wave and Vibration Test
Analysis of a 110 kV Transformer Operation Accident Caused by Failure of On - load Tap Changer