A Novel Fault Line Selection Scheme for Isolated Neutral System When Single - phase Short Circuit Faults Occur Based on Reactive Current
|更新时间:2026-02-13
|
A Novel Fault Line Selection Scheme for Isolated Neutral System When Single - phase Short Circuit Faults Occur Based on Reactive Current
Vol. 42, Issue 2, Pages: 20-23(2019)
作者机构:
国网四川省电力公司电力科学研究院
作者简介:
基金信息:
DOI:
CLC:TM713
Published:2019
稿件说明:
移动端阅览
Li Shilong. A Novel Fault Line Selection Scheme for Isolated Neutral System When Single - phase Short Circuit Faults Occur Based on Reactive Current[J]. 2019, 42(2): 20-23.
DOI:
Li Shilong. A Novel Fault Line Selection Scheme for Isolated Neutral System When Single - phase Short Circuit Faults Occur Based on Reactive Current[J]. 2019, 42(2): 20-23.DOI:
A Novel Fault Line Selection Scheme for Isolated Neutral System When Single - phase Short Circuit Faults Occur Based on Reactive Current
Fault line selection is difficult in isolated neutral system. A novel fault line selection scheme based on reactive current is proposed. After single - phase short circuit faults occur,the current change of fault phase in each line is mainly composed of capacitive current,and the current is reactive current. For fault phase,the reactive current change of fault line is larger than that of normal line. On this basis,the novel fault line selection scheme is proposed. A isolated neutral system model is built in PSCAD to research the reliability of the proposed scheme. The type of transmission line and grounding resistance are considered in simulation. Simulation results show that the proposed scheme can select the fault line with a high reliability.