According to actual operational of a 600 MW unit boiler air preheater
in order to improve coal quality variations and low-load conditions
it proposes a series of retrofit measures.Performance indicators such as air leakage rate of the air preheater
flue gas temperature
hot air temperature
and flue gas and air side resistance are tested after the renovation.After testing
compared with before the renovation
the air leakage rate of the A-side and B-side air preheaters meets the requirement of less than 4%
the decrease in flue gas temperature meets the requirement of not less than 4 ℃
and the decrease in primary air resistance meets the guarantee value requirement of greater than 0.5 kPa
The renovation effect achieved the expected results
which effectively improving the safety and economy of the air preheater and the entire unit operation.It can provide reference for other power plant boiler air preheater reconstruction.