According to a 220 kV porcelain pillar circuit breaker pillar porcelain sleeve crack problem
experimental methods such as macroscopic inspection
crack morphology analysis
energy spectrum detection analysis
X-ray diffraction detection
metallographic analysis
mechanical load test
and finite element analysis are used to analyze the cracked pillar porcelain sleeve.The results show that there is a significant eccentricity in the bonding area of the porcelain sleeve
which would generate a significant additional bending moment on the pillar porcelain sleeve under the self weight of the circuit breaker.At the same time
due to the uneven thickness of the cement bonding
significant internal stress would be generated in the bonding area when it is damp or expanded due to significant temperature changes
leading to the crack of the pillar porcelain sleeve.