In order to improve the accuracy of voltage sag source identification
a voltage sag source identification method based on the improved whale optimization algorithm(IWOA) optimized support vector machine(SVM) is proposed.Firstly
by using S variable losses to process the voltage signal
16 feature quantities are obtained for voltage sag source identification.Secondly
multiple mea-sures such as population chaos initialization
nonlinear convergence factor
and Cauchy mutation are adopted to improve the whale optimization algorithm
resulting in the IWOA algorithm with better convergence performance.The IWOA algorithm is used to search for the optimal parameter values of SVM
and a voltage sag source identification model based on IWOA-SVM is constructed.Six different categories of voltage sag disturbance signals are used for example analysis.The results show that the recognition accuracy of the IWOA-SVM model is as high as 98.33%
and the recognition effect is better than other methods
verifying the effectiveness of the proposed voltage sag source identification method.