A neural network design for black-box identification of converter impedance models in arbitrary operating conditions
|更新时间:2025-10-16
|
A neural network design for black-box identification of converter impedance models in arbitrary operating conditions
Vol. 44, Issue 1, Pages: 2-8(2025)
作者机构:
国网江苏省电力有限公司电力科学研究院,江苏,南京,211103
作者简介:
基金信息:
DOI:
CLC:TM712
Published:2025
稿件说明:
移动端阅览
CHEN Bing. A neural network design for black-box identification of converter impedance models in arbitrary operating conditions[J]. 2025, 44(1): 2-8.
DOI:
CHEN Bing. A neural network design for black-box identification of converter impedance models in arbitrary operating conditions[J]. 2025, 44(1): 2-8.DOI:
A neural network design for black-box identification of converter impedance models in arbitrary operating conditions
The impedance-based method is favored by engineering because it can analyze system stability under conditions with the unknown device control structure or parameters. Considering that the impedance characteristics of AC grid-connected equipment represented by power electronic converters are easily affected by the AC steady-state operating point
quickly deriving an impedance model for any operating condition of the converter using black-box identification can greatly improve the efficiency of stability analysis. The neural network-based can eliminate the limitations of the least squares method-based identification
this paper further improves the neural network design to significantly improve its interpretability. In the data collection stage
the frequency sweep method is used to obtain the frequency response of the closed-loop impedance model under enough operating conditions. In the model training stage
taking into account the latent features of the converter impedance model
a neural network with the same number as the disturbance frequency was designed
and the Levenberg-Marquardt algorithm with Bayesian regularization integrated is used to enhance the generalization ability of the network trained with a small dataset. In the model verification phase
the network is fed with set operating conditions
achieving highly accurate identification of stable operating conditions and offline prediction.