Optimization control strategy for active distribution areas with E-SOP considering energy storage characteristics
|更新时间:2025-10-16
|
Optimization control strategy for active distribution areas with E-SOP considering energy storage characteristics
Vol. 44, Issue 4, Pages: 80-89(2025)
作者机构:
三峡大学电气与新能源学院,湖北,宜昌,443002
作者简介:
基金信息:
DOI:
CLC:TM732
Published:2025
稿件说明:
移动端阅览
YU Weixu. Optimization control strategy for active distribution areas with E-SOP considering energy storage characteristics[J]. 2025, 44(4): 80-89.
DOI:
YU Weixu. Optimization control strategy for active distribution areas with E-SOP considering energy storage characteristics[J]. 2025, 44(4): 80-89.DOI:
Optimization control strategy for active distribution areas with E-SOP considering energy storage characteristics
摘要
针对配电网中分布式电源渗透率提高导致的潮流倒送、电压波动和供电能力不足等问题,文中提出一种基于储能特性的三端智能软开关(three-terminal intelligent soft open point
and insufficient power supply capacity resulting from the increased penetration of distributed generation in distribution networks
an optimized control strategy for active distribution substations incorporating a three-terminal intelligent soft open point (E-SOP) for energy storage is proposed. Firstly
the topology of E-SOP is thoroughly analyzed
and a corresponding mathematical model is established to lay the foundation for subsequent optimization control. Secondly
a site selection and planning model for the E-SOP based on voltage-power sensitivity is proposed to determine its optimal installation location. On this basis
a multi-objective optimization model is developed
aiming to minimize comprehensive costs and voltage deviations
to configure the capacity of the E-SOP. This model is transformed into a second-order cone programming model using conic relaxation techniques and solved iteratively through a particle swarm optimization algorithm. Finally
simulations on an IEEE 33-node flexible interconnected system validate the effectiveness of the proposed strategy
and further simulations on an IEEE 69-node system confirm its applicability and superiority. The results indicate that
compared to traditional systems without E-SOP interconnection
the proposed strategy reduces voltage deviation by 2.24%
daily average system losses by 50.41%
and overall costs by 21.74%
making it suitable for distribution systems of various scales.