M3C)拓扑的双端低频输电系统中,分析低频线路单相接地和两相短路的故障电气特征及相量差动保护适应性;然后,提出一种故障控制策略,通过抑制功率站正序电流输出显化故障特征,改善差动保护动作性能,进而提高保护灵敏度;最后,搭建某低频输电工程实时数字仿真(real-time digital simulator
As a fault occurs on lines of a two-terminal low-frequency transmission system
fault currents will be suppressed when frequency converters adopt negative sequence current suppression strategy. Under such a circumstance
currents on both sides of the line show weak feed and traversal characteristics
leading to poor sensitivity or even failure to operate of the traditional phase-based line differential protection. To solve the above problem
the two-terminal low-frequency transmission system based on modular multilevel matrix converter (M3C) topology is constructed. And the fault electrical characteristics and phasor differential protection adaptability of single-phase grounding and two-phase short-circuit faults of low-frequency lines are analyzed. Then
a fault control strategy is proposed to highlight fault characteristics by suppressing the positive sequence current output of the power control station
thereby improving the braking characteristics and sensitivity of differential protection. Finally
a real-time digital simulator (RTDS) model is built based on a low-frequency transmission project
and the proposed control strategy is simulated and verified against typical faults. The results show that the proposed fault control strategy can effectively solve the problem of insufficient sensitivity of phasor differential protection for low-frequency line fault