Asymmetric fault voltage support scheme for soft open points based on improved negative sequence voltage outer loop
|更新时间:2025-10-16
|
Asymmetric fault voltage support scheme for soft open points based on improved negative sequence voltage outer loop
Vol. 44, Issue 4, Pages: 23-32(2025)
作者机构:
东南大学电气工程学院,江苏,南京,210096
作者简介:
基金信息:
DOI:
CLC:TM464
Published:2025
稿件说明:
移动端阅览
WANG Xuze. Asymmetric fault voltage support scheme for soft open points based on improved negative sequence voltage outer loop[J]. 2025, 44(4): 23-32.
DOI:
WANG Xuze. Asymmetric fault voltage support scheme for soft open points based on improved negative sequence voltage outer loop[J]. 2025, 44(4): 23-32.DOI:
Asymmetric fault voltage support scheme for soft open points based on improved negative sequence voltage outer loop
Flexible interconnection and dynamic power flow regulation in distribution networks are achieved by soft open point (SOP)
optimizing the configuration and scheduling of distribution resources. To improve the load voltage during asymmetric ground faults
it is proposed that positive and negative sequence currents are output by the converter during faults. This provides voltage support and enhances fault ride-through capability. However
actual operating conditions make open-loop optimization schemes susceptible. Poor performance is shown by traditional negative sequence voltage-based closed-loop support. In this paper
the conventional negative sequence voltage outer loop is improved by controlling the amplitude of negative sequence current to suppress the negative sequence voltage. The phase of the negative sequence current is adjusted to optimize the suppression effect. To enhance the inverter's capacity utilization and limit active power fluctuations
a comprehensive scheme is proposed for limiting the positive and negative sequence current amplitudes. A short-circuit fault simulation is constructed using PSCAD simulation software
based on the actual parameters of the distribution network. The simulation results show that the proposed control strategy significantly enhances voltage performance during fault conditions
improving the low-voltage ride-through capability.