Voltage optimization strategy for active distribution network based on distributed photovoltaic cluster control
|更新时间:2025-10-16
|
Voltage optimization strategy for active distribution network based on distributed photovoltaic cluster control
Vol. 44, Issue 3, Pages: 188-200(2025)
作者机构:
南京工程学院电力工程学院,江苏,南京,211167
作者简介:
基金信息:
DOI:
CLC:TM73
Published:2025
稿件说明:
移动端阅览
JIANG Chunrong. Voltage optimization strategy for active distribution network based on distributed photovoltaic cluster control[J]. 2025, 44(3): 188-200.
DOI:
JIANG Chunrong. Voltage optimization strategy for active distribution network based on distributed photovoltaic cluster control[J]. 2025, 44(3): 188-200.DOI:
Voltage optimization strategy for active distribution network based on distributed photovoltaic cluster control
High penetration of distributed photovoltaic causes voltage violation problem in active distribution network. In order to solve this problem
a voltage optimization strategy based on distributed photovoltaic cluster control is proposed for the active distribution network. Firstly
with economic operation as the objective
shiftable load dispatch
the tap positions of on-load tap-changing transformers
and the output of capacitor banks are determined in the day-ahead stage. Subsequently
the approximate voltage sensitivity is calculated based on the day-ahead scheduling results
and clusters are partitioned using the K-means algorithm according to a comprehensive clustering index. Finally
in the intra-day stage
the cluster self-regulation is carried out based on the cluster adjustment characteristics
aiming at minimizing the internal network losses or the node voltage deviations. The inter-cluster coordination optimization is then performed based on the alternating direction multiplier method. Deploy this strategy on the IEEE 33-node system
and conduct a comparative analysis of voltage regulation effectiveness under various weather conditions and different scheduling strategies. The results show that after the day-ahead centralized optimization
the node voltages are within the limit range. After the intra-day rolling optimization
the voltage deviation is further reduced
and the deviation does not exceed 3% on sunny days. The case study results verify that the proposed optimization strategy guarantees voltage quality and meanwhile improves operational efficiency of distribution network.