The Calculation of Short-circuit Current and Research on Design of Grounding Grid in ±1100kV Converter Station with Hierarchical Connection
|更新时间:2026-02-13
|
The Calculation of Short-circuit Current and Research on Design of Grounding Grid in ±1100kV Converter Station with Hierarchical Connection
Vol. 44, Issue 3, Pages: 50-55(2021)
作者机构:
中国电力工程顾问集团中南电力设计院有限公司
作者简介:
基金信息:
DOI:
CLC:TM721
Published:2021
稿件说明:
移动端阅览
ZENG Wei-wen. The Calculation of Short-circuit Current and Research on Design of Grounding Grid in ±1100kV Converter Station with Hierarchical Connection[J]. 2021, 44(3): 50-55.
DOI:
ZENG Wei-wen. The Calculation of Short-circuit Current and Research on Design of Grounding Grid in ±1100kV Converter Station with Hierarchical Connection[J]. 2021, 44(3): 50-55.DOI:
The Calculation of Short-circuit Current and Research on Design of Grounding Grid in ±1100kV Converter Station with Hierarchical Connection
Short circuit current calculation and grounding design both are the important parts of engineering design
which is of great significance to the safe and stable operation of the converter station. In this paper
based on ±1100kV Guquan UHVDC converter station with hierarchical connection
different levels of short-circuit current have been calculated. After considering the shunting effect of short-circuit current via lightning shield wires and the transformer neutral point
the grounding fault current of converter station is calculated. According to the grounding fault current
design scheme of grounding grid for the UHVDC converter station and safety evaluation have been proposed. For converter stations with hierarchical access
the asymmetric short-circuit current should be calculated for different AC buses based on variant operating situations
and the maximum value of short-circuit current should be used to verify the ground grid design indicators.