A case of partial discharge defect in 35 kV switchgear cabinet is analyzed. The live detection technologies such as transient earth voltage
acoustic emission and ultra-high frequency is adopted to detect and analyze the defect
and the electromagnetic wave time difference method is used to locate the partial discharge source. Combined with the internal structure of switchgear cabinet
the location range of the partial discharge source is given. The obvious discharge trace between the lead of A-phase arrester and the insulation board is found during the power failure inspection
which verifies the correctness of the defect diagnosis and positioning result. The results show that the live detection technologies for partial discharge can effectively find insulation defects in switchgear cabinet
which provides experiences for similar defects treatment of switchgear cabinet.
Defect Detection and Analysis of Partial Discharge in 35 kV Switchgear Cabinet
Application of Comprehensive Diagnosis Method for Internal Discharge Defects of GIS Supporting Insulator
Narrowband Interference Suppression of Partial Discharge Based on Short-time Fourier Transform
Development of An Ultrasound Partial Discharge Detection Device
On-site Comprehensive Diagnosis Method of Partial Discharge for Transformer Equipment Based on Ultrasonic Associated with Electromagnetic Wave and Vibration Test
Related Author
Yao Xiao
He Yuhang
Xue Zhihang
Yang Fan
Zhou Dianbo
Xiong Pan
Dai Hui
ZHOU Tao
Related Institution
State Grid Luzhou Electric Power Supply Company
State Grid Sichuan Electric Power Research Institute
Kunming Power Supply Bureau of Yunnan Power Grid Co., Ltd.
Urumqi Electric Power Supply Company,State Grid Xinjiang Electric Power