ONE-DIMENSIONAL CALCULATION METHOD OF THERMAL PERFORMANCE FOR NATURAL DRAFT COUNTER FLOW COOLING TOWER WITH WATER DISTRIBUTION IN THE OUTER AREA
|更新时间:2025-09-28
|
ONE-DIMENSIONAL CALCULATION METHOD OF THERMAL PERFORMANCE FOR NATURAL DRAFT COUNTER FLOW COOLING TOWER WITH WATER DISTRIBUTION IN THE OUTER AREA
Thermal Power GenerationVol. 38, Issue 6, Pages: 24-27(2009)
作者机构:
1. 中国水利水电科学研究院
2. 西北电力设计院
3. 中国电力工程顾问集团公司
作者简介:
基金信息:
DOI:
CLC:TK264.1
Published:2009
稿件说明:
移动端阅览
ZHAO Shun-an1, YANG Ping-zheng2, SHI Cheng3, et al. ONE-DIMENSIONAL CALCULATION METHOD OF THERMAL PERFORMANCE FOR NATURAL DRAFT COUNTER FLOW COOLING TOWER WITH WATER DISTRIBUTION IN THE OUTER AREA[J]. Thermal power generation, 2009, 38(6): 24-27.
DOI:
ZHAO Shun-an1, YANG Ping-zheng2, SHI Cheng3, et al. ONE-DIMENSIONAL CALCULATION METHOD OF THERMAL PERFORMANCE FOR NATURAL DRAFT COUNTER FLOW COOLING TOWER WITH WATER DISTRIBUTION IN THE OUTER AREA[J]. Thermal power generation, 2009, 38(6): 24-27.DOI:
ONE-DIMENSIONAL CALCULATION METHOD OF THERMAL PERFORMANCE FOR NATURAL DRAFT COUNTER FLOW COOLING TOWER WITH WATER DISTRIBUTION IN THE OUTER AREA
摘要
在我国的北方地区
自然通风逆流式冷却塔冬季或春秋季一般采用外区配水的运行方式
塔内的一部分区域不淋水
而此时传统的热力计算方法将不再适用。通过对塔内的热空气密度进行了线性关系及雨滴阻力均匀的简化假设后
推导出了冷却塔外区配水的一维热力计算方法。经与原型实测数据的对比
计算误差不大于0.3℃
吻合良好
可供设计参考。
Abstract
In winter
spring
and autum seasons at norther area in China
the natural draft counter flow cooling towers were generally adopting an operation mode with water tricking in the outer area of the cooling tower
while in a part of the centre area
there isn't water tricking.In this case
however
the traditional calculation method of thermal performance will be unsuitable to use.Through simplified assumption that the density of hot air is changing linearly with the height of tower
and the resistance of rain droplets is even with the their radiuses
an one-dimensional calculation method for thermal performance of cooling towers with water destribution in the outer area has been deduced and obtained.After comparison with the prototype measured data