AN APPROACH TO PROBLEM OF SCRAMBLING FOR AIR OF AXIAL I. D. FANS WITH STATIONARY BLADE ADJUSTMENT
|更新时间:2025-09-28
|
AN APPROACH TO PROBLEM OF SCRAMBLING FOR AIR OF AXIAL I. D. FANS WITH STATIONARY BLADE ADJUSTMENT
Thermal Power GenerationVol. 38, Issue 7, Pages: 57-59(2009)
作者机构:
1. 国电谏壁发电厂
2. 青海桥头铝电有限公司
作者简介:
基金信息:
DOI:
CLC:TK223.26
Published:2009
稿件说明:
移动端阅览
SUN Wen-hua1, HE Sen21.Guodian Jianbi Power Plant. AN APPROACH TO PROBLEM OF SCRAMBLING FOR AIR OF AXIAL I. D. FANS WITH STATIONARY BLADE ADJUSTMENT[J]. Thermal power generation, 2009, 38(7): 57-59.
DOI:
SUN Wen-hua1, HE Sen21.Guodian Jianbi Power Plant. AN APPROACH TO PROBLEM OF SCRAMBLING FOR AIR OF AXIAL I. D. FANS WITH STATIONARY BLADE ADJUSTMENT[J]. Thermal power generation, 2009, 38(7): 57-59.DOI:
AN APPROACH TO PROBLEM OF SCRAMBLING FOR AIR OF AXIAL I. D. FANS WITH STATIONARY BLADE ADJUSTMENT
摘要
针对锅炉运行中存在并联运行引风机"抢风"的问题
从风机性能曲线、工作点角度入手对AN型静叶调节轴流引风机进行了分析。结果表明
由于引风机"抢风"
整个管网的阻力曲线发生了变化
使得风机工作点落入∞形区域内
导致炉膛压力处于不稳定状态甚至使风机出现过电流而损坏。根据实例
对引风机"抢风"的现象、原因进行了分析
并提出了防范措施。
Abstract
In operation of boilers
the problem of "scrambing for air" is existing between the axial induced draft(I.D.) fans connected in parallel operation.Regarding to this
starting from the performance curve and the angle of working point for said fans
the problem of "scrambling for air" concerning AN type axial I.D.fans with stationary blade adjustment has been analysed.Results show that the resistance curve of the whole pipeline network has changed due to "scrambling for air"
making the working point of said fans to be dropped into ∞-shaped region
the "scrambling for air" can make pressure in the furnace to be in an unstable state
even making the fans to be damaged due to occurrence of large electric current.Based on the living examples
the phenomenon
cause
and disposal of problem "scrambling for air" of axial I.D.fans have been explained
OPERATIONAL CHARACTORS OF BOILERS EQUIPPED FOR ULTRA-SUPERCRITICAL 660 MW UNIT AFTER COMBINING THE BOOSTER AIR FAN IN DESULPHURIZATION SYSTEM AND THE INDUCED DRAFT FAN INTO ONE
Flue gas recirculation scheme for double-reheat boilers
CAUSE ANALYSIS ABOUT OVERTEMPERATURE OF RETURN OIL FROM HYDRAULIC COUPLING OF I.D.FANS
ECONOMIC ANALYSIS ON SINGLE ROW CONFIGURATION OF FORCED, INDUCED,AND PRIMARY AIR FANS FOR A 600 MW BOIELR
Flue duct optimization for integration of induced draft fan and booster fan
Related Author
CHEN Xing
ZHOU Liguo Datang Xinyang Hua'yu Power Generation Co Ltd