ANALYSIS OF ABNORMAL POWER FLUCTUATION RESULTED FROM LOW EXCITION LIMIT IN EXCITATION OF 300MW UNIT
|更新时间:2025-09-28
|
ANALYSIS OF ABNORMAL POWER FLUCTUATION RESULTED FROM LOW EXCITION LIMIT IN EXCITATION OF 300MW UNIT
Thermal Power GenerationVol. 38, Issue 12, Pages: 75-77(2009)
作者机构:
巴蜀江油发电厂
作者简介:
基金信息:
DOI:
CLC:TM621
Published:2009
稿件说明:
移动端阅览
WANG Qing-ming Bashu Jiangyou Power Plant. ANALYSIS OF ABNORMAL POWER FLUCTUATION RESULTED FROM LOW EXCITION LIMIT IN EXCITATION OF 300MW UNIT[J]. Thermal power generation, 2009, 38(12): 75-77.
DOI:
WANG Qing-ming Bashu Jiangyou Power Plant. ANALYSIS OF ABNORMAL POWER FLUCTUATION RESULTED FROM LOW EXCITION LIMIT IN EXCITATION OF 300MW UNIT[J]. Thermal power generation, 2009, 38(12): 75-77.DOI:
ANALYSIS OF ABNORMAL POWER FLUCTUATION RESULTED FROM LOW EXCITION LIMIT IN EXCITATION OF 300MW UNIT
In debugging process of 168 h trial operation for unit no.2 in second-phase project of Bashu Jiangyou Power Plant(2×300 MW units)
power oscillation had appeared
resulting in abnormal fluctuation of power and voltage in a large region of 500 kV power grid in Sichuan Province.Through analysis
it is believed that the causes leading to above-mentioned abnormal fluctuation of power and voltage are as follows:(1)in the stage of sliding parameter operation for starting up the unit
the valve-position control mode was used
and the governing valve being put into the "whole open"position
the target value of load being too high;(2)the slope of original low excitation limit curve was too large;(3)after occurrence of fluctuation
the reactive load hadn't timely increased
on the contrary
the active load of the unit was still increasing.Regarding to this
the curve of low excitation limit has been modified