ANALYSIS OF VIBRATION PROBLEM DURING GOVENOR VALVE SWITCHING IN THE CONTROL MODE OF ONE 600 MW STEAM TURBINE UNIT AND OPTIMIZATION OF ITS STEAM DISTRIBUTION
|更新时间:2025-09-28
|
ANALYSIS OF VIBRATION PROBLEM DURING GOVENOR VALVE SWITCHING IN THE CONTROL MODE OF ONE 600 MW STEAM TURBINE UNIT AND OPTIMIZATION OF ITS STEAM DISTRIBUTION
Thermal Power GenerationVol. 38, Issue 12, Pages: 68-72(2009)
作者机构:
广东电力科学研究院
作者简介:
基金信息:
DOI:
CLC:TK268.1
Published:2009
稿件说明:
移动端阅览
KAN Wei-min, DENG Shao-xiang, TIAN Feng, et al. ANALYSIS OF VIBRATION PROBLEM DURING GOVENOR VALVE SWITCHING IN THE CONTROL MODE OF ONE 600 MW STEAM TURBINE UNIT AND OPTIMIZATION OF ITS STEAM DISTRIBUTION[J]. Thermal power generation, 2009, 38(12): 68-72.
DOI:
KAN Wei-min, DENG Shao-xiang, TIAN Feng, et al. ANALYSIS OF VIBRATION PROBLEM DURING GOVENOR VALVE SWITCHING IN THE CONTROL MODE OF ONE 600 MW STEAM TURBINE UNIT AND OPTIMIZATION OF ITS STEAM DISTRIBUTION[J]. Thermal power generation, 2009, 38(12): 68-72.DOI:
ANALYSIS OF VIBRATION PROBLEM DURING GOVENOR VALVE SWITCHING IN THE CONTROL MODE OF ONE 600 MW STEAM TURBINE UNIT AND OPTIMIZATION OF ITS STEAM DISTRIBUTION
摘要
某电厂5号机为上海汽轮机厂生产的亚临界600MW汽轮机组
在单阀、顺序阀控制方式的切换过程中发现高压转子振动明显增大
严重影响机组的安全经济运行。结合振动测试
分析了配汽方式对轴系振动的影响;根据阀门特性试验
优化调节阀开启顺序。采用优化后的顺序阀方案
顺利地实现了机组的调节阀控制方式的切换
并且轴系振动稳定
有效地提高了机组运行的安全经济性。
Abstract
The turbine no.5 in one power plant is a subcritical pressrue 600 MW unit manufactured by the shanghai Turbine Works.During the valve switching process in control mode from single valve operation to sequence valve operation
the shaft vibration of high-pressrue cylinder is substantially increased
affecting seriously safe and economic operation of the unit.Combining with vibration test
the influence of steam distribution mode upon the vibration of shaft system has been analysed.Based on the characteristic test of valves
the open sequence of govenor valve has been optimized.Adopting the optimized scheme of valve-opening sequence
the switching in control mode of the govenor valve has been successfully realized
and the vibration of shaft system being stabilized
enhancing effectively the safety and economic efficiency in operation of the unit.
FEATURES OF SHAFTING SYSTEM FOR THE FIRST SUPERCRITICAL 600MW TURBO-GENERATOR SET MANUFACTURED BY BAPE CORPORATION,AS WELL AS VIBRATION ANALYSIS AND DISPOSAL THEREOF
ANALYSIS OF VIBRATION PROBLEM FOR HOME - MADE 600 MW SUPERCRITICAL TURBO - GENERATOR SET AND TREATMENT THEREOF
IMPROVEMENT OF RB CONTROL FOR DIRECT FIRING BOILER EQUIPED WITH BLOWER COAL PULVERIZED
LOGIC OPTIMIZATION OF FEED WATER PUMP INTERLOCK OF AIR-COOL 600 MW UNIT
THE OPTIMIZATION STRATEGY OF COORDINATED CONTROL SYSTEM FOR 600 MW THERMAL POWER PLANT