ANALYSIS OF ABNORMAL TEMPERATURE FOR FLUE GAS EXHAUSTED FROM 475t/h CFB BOILER IN JINGDEZHEN POWER PLANT
|更新时间:2025-09-28
|
ANALYSIS OF ABNORMAL TEMPERATURE FOR FLUE GAS EXHAUSTED FROM 475t/h CFB BOILER IN JINGDEZHEN POWER PLANT
Thermal Power GenerationVol. 38, Issue 11, Pages: 70-72(2009)
作者机构:
1. 江西省电力科学研究院
2. 江西省电力高级技校
作者简介:
基金信息:
DOI:
CLC:TK223.34
Published:2009
稿件说明:
移动端阅览
ZHU Yun-peng1, ZHU Yu21.Jiangxi Provincial Electric Power Science Research Insitute. ANALYSIS OF ABNORMAL TEMPERATURE FOR FLUE GAS EXHAUSTED FROM 475t/h CFB BOILER IN JINGDEZHEN POWER PLANT[J]. Thermal power generation, 2009, 38(11): 70-72.
DOI:
ZHU Yun-peng1, ZHU Yu21.Jiangxi Provincial Electric Power Science Research Insitute. ANALYSIS OF ABNORMAL TEMPERATURE FOR FLUE GAS EXHAUSTED FROM 475t/h CFB BOILER IN JINGDEZHEN POWER PLANT[J]. Thermal power generation, 2009, 38(11): 70-72.DOI:
ANALYSIS OF ABNORMAL TEMPERATURE FOR FLUE GAS EXHAUSTED FROM 475t/h CFB BOILER IN JINGDEZHEN POWER PLANT
such as high flue gas temperature from the air preheater
high temperature of the hot air
large deviation of the exhaust flue gas temperature at A and B side etc.
have recently appeared in operation of 475 t/h CFB boiler in Jingdezhen Power Plant.For this
analysis from aspects of air leakage in the air preheater proper
effects from the flue gas side
and effects from the air side
etc.
has been carried out.Results of analysis show that the main causes leading to the above-mentioned phenmena are as follows:inlet air temperature of the air preheater in practical operation isn't conform to the designed value
and the flow rate of primary air in the process of operation is deviated from the designed value.Hence
improving measures and recommendations
such as strenthening combustion adjustment in operation
ensuring the flow rate of primary air to be about 60%
intensifying inspection and leakage-plugging at A side
and doing best to eliminate air leakage of the air preheater