ANALYSIS OF VIOLENT VIBRATION AND HIGH NOISE OCCURRED ON DESUPERHEATING WATER PIPE-LINE TO DRAIN FLASH TANK
|更新时间:2025-09-28
|
ANALYSIS OF VIOLENT VIBRATION AND HIGH NOISE OCCURRED ON DESUPERHEATING WATER PIPE-LINE TO DRAIN FLASH TANK
Thermal Power GenerationVol. 39, Issue 4, Pages: 95-96(2010)
作者机构:
华能珞璜发电有限责任公司
作者简介:
基金信息:
DOI:
CLC:TB53;TM621
Published:2010
稿件说明:
移动端阅览
JIANG Jili, YUAN ChenghuaiHuaneng Luohuang Power Generation Co Ltd. ANALYSIS OF VIOLENT VIBRATION AND HIGH NOISE OCCURRED ON DESUPERHEATING WATER PIPE-LINE TO DRAIN FLASH TANK[J]. Thermal power generation, 2010, 39(4): 95-96.
DOI:
JIANG Jili, YUAN ChenghuaiHuaneng Luohuang Power Generation Co Ltd. ANALYSIS OF VIOLENT VIBRATION AND HIGH NOISE OCCURRED ON DESUPERHEATING WATER PIPE-LINE TO DRAIN FLASH TANK[J]. Thermal power generation, 2010, 39(4): 95-96.DOI:
ANALYSIS OF VIOLENT VIBRATION AND HIGH NOISE OCCURRED ON DESUPERHEATING WATER PIPE-LINE TO DRAIN FLASH TANK
The phenomena of violent vibration and high noise occurred on desuperheating water pipeline to the drain flash tank of 2×600MW units in second-phase project of Huaneng Luohuang Power Generation Co Ltd have been analysed
it is believed from test and analysis that the main cause resulting in violent vibration and high noise on desuperheating water pipeline is the larger aperture of desuperheating water spraying pipe.Through retrofitting the number and apecture of spray-holes on the desuperheating water spraying pipe
the problem of violent vibration and high noise occurred on the desuperheating water pipeline has been successfully eliminated.