DESIGN AND APPLICATION OF A NEW BYPASS CONTROL STRATEGY FOR UNITS
Directing against the problems existing in many power plants
i.e.the bypass system of units is unable to bring its protective effects into full play
and only used as a drain valve of boiler and steam turbine in the stage of start-up or shutdown of units
a new bypass control strategy has been designed
which devides the HP-bypass into five control modes
the whole process automatic control of bypass system
from start-up of unit to connet the unit onto power grid
and returned again to sectionalization and shutdown of boiler
can be realized.Through calculation of steam's enthalpy drop before and after the LP-bypass system
the quantity of desuperheating water required by the LP-pass system can be precisely pre-estimated
thereby the exhaust steam from the LP-bypass system can be ensured to satisfy the requirement in operation of condenser.The above-mentioned control strategy has been applied onto an ultra-supercritical 1 000 MW unit in second-phase project of Ninghai Power Plant
the fast cut back (FCB) of unit without boiler shutdown being realized;after finishing assessment test of the bypass system
the unit is reconnected onto the power grid within 0 min
and the load of unit being increased to 480 MW after 15 min.