CONTROL STRATEGY OF RETROFITTING MOTOR-DRIVEN FEED WATER PUMP INTO TURBINE-DRIVEN FEED WATER PUMP FOR 300 MW UNITS AND APPLICATION THEREOF
|更新时间:2025-09-28
|
CONTROL STRATEGY OF RETROFITTING MOTOR-DRIVEN FEED WATER PUMP INTO TURBINE-DRIVEN FEED WATER PUMP FOR 300 MW UNITS AND APPLICATION THEREOF
Thermal Power GenerationVol. 39, Issue 8, Pages: 85-87(2010)
作者机构:
1. GE新华控制工程有限公司
2. 西安热工研究院有限公司
3. 华能淮阴电厂
作者简介:
基金信息:
DOI:
CLC:TM621
Published:2010
稿件说明:
移动端阅览
WANG Yanjie1, ZHAO Zhidan2, WU Lianjun3, et al. CONTROL STRATEGY OF RETROFITTING MOTOR-DRIVEN FEED WATER PUMP INTO TURBINE-DRIVEN FEED WATER PUMP FOR 300 MW UNITS AND APPLICATION THEREOF[J]. Thermal power generation, 2010, 39(8): 85-87.
DOI:
WANG Yanjie1, ZHAO Zhidan2, WU Lianjun3, et al. CONTROL STRATEGY OF RETROFITTING MOTOR-DRIVEN FEED WATER PUMP INTO TURBINE-DRIVEN FEED WATER PUMP FOR 300 MW UNITS AND APPLICATION THEREOF[J]. Thermal power generation, 2010, 39(8): 85-87.DOI:
CONTROL STRATEGY OF RETROFITTING MOTOR-DRIVEN FEED WATER PUMP INTO TURBINE-DRIVEN FEED WATER PUMP FOR 300 MW UNITS AND APPLICATION THEREOF
Directing against retrofitting original feed water system(having three motor-driven feed water pumps) of 330 MW unit in Huai'yin Power Plant into a feed waster system with one turbine-driven feed water pump and two motor-driven feed water pumps
a new set of feed water control system has been designed.In order to ensure the real-time control of feed water system in case of one turbine-driven feed water pump being in operation and two motor-driven feed water pumps being standby
the trip of turbine-driven feed water pump
the operation of motor-driven feed water pumps
as well as their control interlocking signals are connected to the control system by using hardwires
results of application show that the new feed water control systme has good control quality.