OPTIMIZATION OF THE COMBUSTION CONTROL SYSTEM FOR BOILERS EQUIPPED WITH 330 MW UNIT IN SHENHUA GUOHUA ZHUNGE'R POWER PLANT
|更新时间:2025-09-28
|
OPTIMIZATION OF THE COMBUSTION CONTROL SYSTEM FOR BOILERS EQUIPPED WITH 330 MW UNIT IN SHENHUA GUOHUA ZHUNGE'R POWER PLANT
Thermal Power GenerationVol. 39, Issue 7, Pages: 62-64(2010)
作者机构:
神华国华准格尔电厂
作者简介:
基金信息:
DOI:
CLC:TK223.72
Published:2010
稿件说明:
移动端阅览
WANG Guanding, WANG Wenbin, AN Huiyong, et al. OPTIMIZATION OF THE COMBUSTION CONTROL SYSTEM FOR BOILERS EQUIPPED WITH 330 MW UNIT IN SHENHUA GUOHUA ZHUNGE'R POWER PLANT[J]. Thermal power generation, 2010, 39(7): 62-64.
DOI:
WANG Guanding, WANG Wenbin, AN Huiyong, et al. OPTIMIZATION OF THE COMBUSTION CONTROL SYSTEM FOR BOILERS EQUIPPED WITH 330 MW UNIT IN SHENHUA GUOHUA ZHUNGE'R POWER PLANT[J]. Thermal power generation, 2010, 39(7): 62-64.DOI:
OPTIMIZATION OF THE COMBUSTION CONTROL SYSTEM FOR BOILERS EQUIPPED WITH 330 MW UNIT IN SHENHUA GUOHUA ZHUNGE'R POWER PLANT
Directing against the difficult problem for putting the correction of secondary air flow rate and oxygen content in flue gas of boilers equipped with 2×330 MW units into automitic control mode
the optimization of combustion control system for said boilers has been carried out;the pressure control of secondary air at oullet of the air preheater being changed from fixed value control to slide pressure control along with load variation of the units;the correction of open dagree for secondary air damper in the oxygen-correcting circuit has been changed to correct the secondary air pressure;the secondary air damper at each level is controlled by open-loop according to coal feed commands of corresponding coal pulverizer.After optimization
the economic efficiency of boilers has been substantially enhanced
the temperature of discharged flue gas being decreased by 4.03 ℃
the coal consumption of units being lowered by 0.19 g/(kW·h)
the power consumption of primary air fan being decreased 0.30%
the power consumption of forced draft fan being lowered 0.03%
the power consumption of induced draft fan being decreased 0.10%
the auxiliary power comsumption in whole plant being lowered by 0.43%.