ANALYSIS AND TREATMENT OF VOLUME RESISTIVITY EXCEEDING SET STANDARD FOR FIRE-RESISTANT OIL MADE FROM PHOSPHATE ESTERS
|更新时间:2025-09-28
|
ANALYSIS AND TREATMENT OF VOLUME RESISTIVITY EXCEEDING SET STANDARD FOR FIRE-RESISTANT OIL MADE FROM PHOSPHATE ESTERS
Thermal Power GenerationVol. 40, Issue 1, Pages: 76-78(2011)
作者机构:
1. 河南电力试验研究院
2. 郑州裕中能源有限责任公司
作者简介:
基金信息:
DOI:
CLC:TM621
Published:2011
稿件说明:
移动端阅览
ZHAO Ruiju1, WU Shihang21.Henan Electric Power Testing & Research Institute. ANALYSIS AND TREATMENT OF VOLUME RESISTIVITY EXCEEDING SET STANDARD FOR FIRE-RESISTANT OIL MADE FROM PHOSPHATE ESTERS[J]. Thermal power generation, 2011, 40(1): 76-78.
DOI:
ZHAO Ruiju1, WU Shihang21.Henan Electric Power Testing & Research Institute. ANALYSIS AND TREATMENT OF VOLUME RESISTIVITY EXCEEDING SET STANDARD FOR FIRE-RESISTANT OIL MADE FROM PHOSPHATE ESTERS[J]. Thermal power generation, 2011, 40(1): 76-78.DOI:
ANALYSIS AND TREATMENT OF VOLUME RESISTIVITY EXCEEDING SET STANDARD FOR FIRE-RESISTANT OIL MADE FROM PHOSPHATE ESTERS
The quality rariation of fire-resistant oil may occurred in operation has been analysed
result of analysis shows that the resistivity
the foaming behavior
and the air-releasing value of fire-resistant oil used for units no.1 and no.2 in one power plant all have exceeded the set standard
after on-line treatment of the fire-resistant oil in said power plant by using a special oil-filtering machine for regeneration-adsorption of the fire-resistant oil
the problem of volume resisitivity exceeding set standard for the fire-resistant oil has been resolved.