TEST STUDY ON DYNAMIC SIMULATION FOR USING CANAL WATER AS INTAKING WATER FOR REVERSE-OSMOSIS SYSTEM
|更新时间:2025-09-28
|
TEST STUDY ON DYNAMIC SIMULATION FOR USING CANAL WATER AS INTAKING WATER FOR REVERSE-OSMOSIS SYSTEM
Thermal Power GenerationVol. 40, Issue 3, Pages: 28-33(2011)
作者机构:
1. 西安热工研究院有限公司
2. 山西省电力建设四公司
作者简介:
基金信息:
DOI:
CLC:TM621.8
Published:2011
稿件说明:
移动端阅览
XU Jianxue1, ZHAO Chenghong2, PEI Sheng1, et al. TEST STUDY ON DYNAMIC SIMULATION FOR USING CANAL WATER AS INTAKING WATER FOR REVERSE-OSMOSIS SYSTEM[J]. Thermal power generation, 2011, 40(3): 28-33.
DOI:
XU Jianxue1, ZHAO Chenghong2, PEI Sheng1, et al. TEST STUDY ON DYNAMIC SIMULATION FOR USING CANAL WATER AS INTAKING WATER FOR REVERSE-OSMOSIS SYSTEM[J]. Thermal power generation, 2011, 40(3): 28-33.DOI:
TEST STUDY ON DYNAMIC SIMULATION FOR USING CANAL WATER AS INTAKING WATER FOR REVERSE-OSMOSIS SYSTEM
The organic matter content in water of Jing-Hang Canal is higher
hence
the water in said canal can't directly be used as intaking water for reverse-osmosis system.For this
based on static test
a test of dynamic simulation has been carried out.The test system is mainly constituted from two-stage coagulating clarifier
a fine sand filter
and two-stage activated carbon filter.Based on the results of test
technological parameters suitable for pretreatment of the canal water have been put forward
including mainly the upward flow rate in first-stage clarifier
the return flow ratio of sludge
the upward flow rate in secondary-stage clarifier
the dosage of cuagulant
coagulation aid
low turbidity additive
and powdered activated carbon etc.
as well as type selection of the activated carbon.At the same time
the limited concentration of organic matters in the canal water used as intaking water forreverse-osmosis system in said technology has been determined.Results of test show that the quality of effluent water from the system can satisfy the requirements of intaking water of reverse-osmosis system under condition of the maximum value of CODMn in the raw water being 17.62 mg/L
INFLUENCE OF PURIFIED FLUE GAS DISCHAR-GING FROM FGD FACILITY THROUGH COOLING TOWER UPON QUALITY OF CIRCULATORY COOLING WATER AND STUDY ON COUNTER MEASURES THE REOF
STUDY ON INFLUENCE OF BACTERICIDE IN CIRCULATING WATER UPON THE REVERSE-OSMOSIS MEMBRANE
JUDGEMENT METHOD OF SCALING TENDENCY FOR CIRCULATING COOLING WATER
TEST STUDY ON SOLIDIFICATION PRETREATMENT TECHNOLOGY OF TERMINAL WASTE-WATER FROM COAL-FIRED POWER PLANTS
Water quality characteristics and reuse treatment process of flue gas condensate in lignite-fired boilers
Related Author
LUO Jiang-he
ZENG De-yong
REN Zhigang41.Xi'an Thermal Power Research Institute Co Ltd