ANALYSIS OF THERMAL ECONOMIC EFFICIENCY FOR SUPERCRITICAL 600 MW UNIT UNDER CONSTANT POWER OUTPUT
|更新时间:2025-09-28
|
ANALYSIS OF THERMAL ECONOMIC EFFICIENCY FOR SUPERCRITICAL 600 MW UNIT UNDER CONSTANT POWER OUTPUT
Thermal Power GenerationVol. 40, Issue 4, Pages: 9-12(2011)
作者机构:
1. 河南省电力勘测设计院
2. 山东商业职业技术学院
作者简介:
基金信息:
DOI:
CLC:TM621
Published:2011
稿件说明:
移动端阅览
CHENG Zutian1, XI Zhenkui21.Henan Provincial Survey & Design Institute. ANALYSIS OF THERMAL ECONOMIC EFFICIENCY FOR SUPERCRITICAL 600 MW UNIT UNDER CONSTANT POWER OUTPUT[J]. Thermal power generation, 2011, 40(4): 9-12.
DOI:
CHENG Zutian1, XI Zhenkui21.Henan Provincial Survey & Design Institute. ANALYSIS OF THERMAL ECONOMIC EFFICIENCY FOR SUPERCRITICAL 600 MW UNIT UNDER CONSTANT POWER OUTPUT[J]. Thermal power generation, 2011, 40(4): 9-12.DOI:
ANALYSIS OF THERMAL ECONOMIC EFFICIENCY FOR SUPERCRITICAL 600 MW UNIT UNDER CONSTANT POWER OUTPUT
摘要
火电机组的热经济性分析是机组节能运行的依据
对超临界600 MW机组建立了热力系统定功率矩阵方程
并进行了热经济性分析。基于热力系统定功率分析方法
分析了加热器端差增大对机组热经济性的影响。分析表明
第1级加热器给水端差增大
直接降低了给水焓值
使得锅炉吸热量增加
所以1号加热器给水端差对机组的热经济性影响最大。
Abstract
Analysis of thermal economic efficiency of the coal-fired units is the basis of energy-saving operation for untis.The matrix equation for thermodynamic system of supercritical 600 MW unit under constant power output has been established
and the thermal economic efficiency being analysed.Based on the method of analysis for thermodynamic system under constant power output
the influence of increasing heater's terminal temperature difference upon the thermal economic efficiency has been analysed.Analysis shows that the increase of terminal temperature difference for feed-water of the first-stage heater decreases directly the enthalpy value of feed-water
making the absorbed heat of boiler to be increased
therefore
the influence of terminal temperature difference of feed-water through heater no.1 upon the thermal economic efficiency is the maximum.
SEVERAL PROBLEMS NEEDING TO PAY ATTENTION FOR CHEMICAL SUPERVISION IN CAPITAL CONSTRUCTION COMMISSIONING OF SUPERCRITICAL 600MW UNIT
CONTROL OPTIMIZATION OF MAIN AUTOMATIC REGULATING SYSTEMS FOR HOME-MADE SUPERCRITICAL 600 MW UNIT
APPLICATION OF PLANT-LEVEL SUPERVISORY INFORMATION SYSTEM FOR SUPERCRITICAL UNIT IN YAOMENG POWER PLANT
INFLUENCE OF THERMAL RESISTANCE DUE TO FOULING OCCURRED IN RADIATORS'TUBEBANDLE OF THE AIR-COOLED CONDENSOR UPON THERMAL ECONOMIC EFFICINECY OF 600 MW DIRECT AIR-COOLED UNIT
ANALYSIS OF OVER-TEMPERATURE ON THE PLATEN SUPERHEATER OF ONCE-THROUGH BOILER FOR SUPERCRITICAL 600 MW UNIT
Related Author
DAI Chuan-long
DIAO Bao-shengGuodian Changzhou Power Generation Co Ltd
ZHU Xiao-xing
XUN Xin
WANG Bai-chun
LIU Wu-lin
LI Jing-baiHunan Provincial Electric Power Testing & Research Institute
ZHANG Yi1
Related Institution
Guodian Changzhou Power Generation Co., Ltd
Hunan Electric Power Test and Research Institute
Yaomeng Second Power Generation Co., Ltd
Xi'an Thermal Power Research Institute Co., Ltd
Energy Research Institute of Shandong Academy of Sciences