INFLUENCE OF USING OVER SPEED PROTECTION CONTROL OF STEAM TURBINE UPON THE FREQUENCY IN POWER GRID AND COUNTERMEASURES THEREOF
|更新时间:2025-09-28
|
INFLUENCE OF USING OVER SPEED PROTECTION CONTROL OF STEAM TURBINE UPON THE FREQUENCY IN POWER GRID AND COUNTERMEASURES THEREOF
Thermal Power GenerationVol. 40, Issue 12, Pages: 70-72(2011)
作者机构:
1. 甘肃电力科学研究院
2. 哈尔滨工业大学电气工程及自动化学院
3. 兰州理工大学电气工程与信息工程学院
作者简介:
基金信息:
DOI:
CLC:TM311;TM711
Published:2011
稿件说明:
移动端阅览
MA Chengxia1, WANG Hongwei1, QIN Rui1, et al. INFLUENCE OF USING OVER SPEED PROTECTION CONTROL OF STEAM TURBINE UPON THE FREQUENCY IN POWER GRID AND COUNTERMEASURES THEREOF[J]. Thermal power generation, 2011, 40(12): 70-72.
DOI:
MA Chengxia1, WANG Hongwei1, QIN Rui1, et al. INFLUENCE OF USING OVER SPEED PROTECTION CONTROL OF STEAM TURBINE UPON THE FREQUENCY IN POWER GRID AND COUNTERMEASURES THEREOF[J]. Thermal power generation, 2011, 40(12): 70-72.DOI:
INFLUENCE OF USING OVER SPEED PROTECTION CONTROL OF STEAM TURBINE UPON THE FREQUENCY IN POWER GRID AND COUNTERMEASURES THEREOF
The traditional overspeed protection control(OPC) uner operation state of isolated power grid may make the govener valve of steam turbine to be frequently actuated due to large fluctuation in rotation speed of the steam turbine
affecting the stability of frequency in power grid.For this
taking the reheated steam turbine as example
a mathematical model for emulating the multiregional single machine infinite system has been established
the influence of different set values of OPC upon the stability of frequency in power grid under operation state of isolated power grid has been emulated
the measures of suitably enhancing the set value of OPC during the time of decoupling the units being put forward
SIMPLIFIED FINITEELEMENT CALCULATION MODEL OF TEMPERATURE FIELD FOR STEAM TURBINE ROTOR
APPLICATION OF SOLID SELF-LUBRICATING TECHNOLOGY IN POWER PLANTS
STUDY ON CONTROL SYSTEM SETTING OF DOUBLE EXTRACTION ADJUSTABLE STEAM TURBINE
ANALYSIS OF FAULTS OCCURRED IN SYNCHRONIZATION WITH POWER NETWORK FOR TAKING INITIAL LOAD BY STEAM TURBINE OF A 180MW GAS AND STEAM TURBINE COMBINED CYCLE UNIT
CAUSE ANALYSIS AND IMPROVEMENT MEASURES FOR PRESSURE REDUCTION OF LUBRICANT OIL DURING STARTUP OF 300MW UNITS