THE MEASUREMENT TEST AND THREE-DIMENSIONAL CALCULATION OF WALL-TEMPERATURE FOR PLATEN SUPERHEATER OF BOILER EQUIPPED FOR 600 MW UNIT
|更新时间:2025-09-28
|
THE MEASUREMENT TEST AND THREE-DIMENSIONAL CALCULATION OF WALL-TEMPERATURE FOR PLATEN SUPERHEATER OF BOILER EQUIPPED FOR 600 MW UNIT
Thermal Power GenerationVol. 40, Issue 6, Pages: 13-16(2011)
作者机构:
1. 河南省电力勘测设计院
2. 武汉大学动力与机械学院
作者简介:
基金信息:
DOI:
CLC:TK223.32
Published:2011
稿件说明:
移动端阅览
XU Haichuan1, PAN Cheng1, CHENG Zutian1, et al. THE MEASUREMENT TEST AND THREE-DIMENSIONAL CALCULATION OF WALL-TEMPERATURE FOR PLATEN SUPERHEATER OF BOILER EQUIPPED FOR 600 MW UNIT[J]. Thermal power generation, 2011, 40(6): 13-16.
DOI:
XU Haichuan1, PAN Cheng1, CHENG Zutian1, et al. THE MEASUREMENT TEST AND THREE-DIMENSIONAL CALCULATION OF WALL-TEMPERATURE FOR PLATEN SUPERHEATER OF BOILER EQUIPPED FOR 600 MW UNIT[J]. Thermal power generation, 2011, 40(6): 13-16.DOI:
THE MEASUREMENT TEST AND THREE-DIMENSIONAL CALCULATION OF WALL-TEMPERATURE FOR PLATEN SUPERHEATER OF BOILER EQUIPPED FOR 600 MW UNIT
The tube-burst of superheater in large-capacity boilers is an improtant factor resulting in forced shutdown of units
and a large number of tube-burst are caused by overtemperature of tube walls.Hence
in order to accurately understand the wall temperature distribution on platen superheater of the boiler
a measurement test of inner and outer wall temperature has been carried out on the platen superheater of boiler equipped for a supercritical 600 MW unit in Dabieshan Power Plant
collecting in real-time the data variation of wall temperature inside and outside the furnace
finding out the relationship between wall temperatures of platen superheater inside and outside the furnace
and a cognate model between them being given by using the fitting method
and calculation and analysis of three-dimensional wall-temperature distribution being carried out.By using the cognate model developed forthe platen superheater's wall temperature inside and outside the furnace and the temperature to measured at measuring points retainable for a long time outside the furnace
the temperature of overtemperature tube-section inside the furnace can be predicted.Besides
the reliability of results obtained from computing program for three-dimensional wall temperature of the platen superheater can also be verified by using said model.