APPLICATION OF ZERO WASTEWATER DISCHARGING SYSTEM IN A POWER PLANT WITH AIR-COOLED UNITS SITUATED IN NORTHERN CHINA
|更新时间:2025-09-28
|
APPLICATION OF ZERO WASTEWATER DISCHARGING SYSTEM IN A POWER PLANT WITH AIR-COOLED UNITS SITUATED IN NORTHERN CHINA
Thermal Power GenerationVol. 40, Issue 10, Pages: 74-77(2011)
作者机构:
西安热工研究院有限公司
作者简介:
基金信息:
DOI:
CLC:TM621.8
Published:2011
稿件说明:
移动端阅览
SU Yan, XU Zhen, WANG Zhengjiang, et al. APPLICATION OF ZERO WASTEWATER DISCHARGING SYSTEM IN A POWER PLANT WITH AIR-COOLED UNITS SITUATED IN NORTHERN CHINA[J]. Thermal power generation, 2011, 40(10): 74-77.
DOI:
SU Yan, XU Zhen, WANG Zhengjiang, et al. APPLICATION OF ZERO WASTEWATER DISCHARGING SYSTEM IN A POWER PLANT WITH AIR-COOLED UNITS SITUATED IN NORTHERN CHINA[J]. Thermal power generation, 2011, 40(10): 74-77.DOI:
APPLICATION OF ZERO WASTEWATER DISCHARGING SYSTEM IN A POWER PLANT WITH AIR-COOLED UNITS SITUATED IN NORTHERN CHINA
The zero wastewater discharging system in a power plant with air-cooled units situated in Northern China adopts a wastewater treatment process as in the following:air floation for oil removalwater softening using limegravity filter tankwater softening by ion exchangereverse osmosis.The technological process has been briefly presented
and the performance test of main treatment equipments being carried out.The results of test show that the quality indices of effluent water from said zero discharging system reaches the requirement of design
however
the self-using water for water softening system with ion exchange is 7.03%
being higher than the designed value of≤5%.In addition
the reverse osmosis facility uses membrane with highest desalting rate at pH value 6~8