INFLUENCE OF FLOW COLLECTOR RETROFIT UPON PERFORMANCE OF CENTRIFUGAL AIR FANS
|更新时间:2025-09-28
|
INFLUENCE OF FLOW COLLECTOR RETROFIT UPON PERFORMANCE OF CENTRIFUGAL AIR FANS
Thermal Power GenerationVol. 40, Issue 10, Pages: 38-42(2011)
作者机构:
西安热工研究院有限公司
作者简介:
基金信息:
DOI:
CLC:TK223.26
Published:2011
稿件说明:
移动端阅览
SUN Dawei, DONG Kangtian, ZHENG Jin, et al. INFLUENCE OF FLOW COLLECTOR RETROFIT UPON PERFORMANCE OF CENTRIFUGAL AIR FANS[J]. Thermal power generation, 2011, 40(10): 38-42.
DOI:
SUN Dawei, DONG Kangtian, ZHENG Jin, et al. INFLUENCE OF FLOW COLLECTOR RETROFIT UPON PERFORMANCE OF CENTRIFUGAL AIR FANS[J]. Thermal power generation, 2011, 40(10): 38-42.DOI:
INFLUENCE OF FLOW COLLECTOR RETROFIT UPON PERFORMANCE OF CENTRIFUGAL AIR FANS
the causes leading to low performance in operation of centrifugal air fans in one power plant has been studied.The study shows that the influence of flow collector upon the aerodynamic flow field inside the impeller is very large.The bad matching between the flow collector and the impeller can affect the actual performance of air fans
the deviation existing in structures of actual flow collector and designed flow collector is the main cause resulting in low performance in operation of air fans.After retrofitting the flow collector
the performance of air fans in operation reaches the designed value.