CAUSE ANALYSIS OF HIGH-TEMPERATURE CORROSION OCCURRED ON THE WATER-WALL OF 1025 t/h BOILER AND SOLVING MEASURES THEREOF
|更新时间:2025-09-28
|
CAUSE ANALYSIS OF HIGH-TEMPERATURE CORROSION OCCURRED ON THE WATER-WALL OF 1025 t/h BOILER AND SOLVING MEASURES THEREOF
Thermal Power GenerationVol. 41, Issue 2, Pages: 53-55(2012)
作者机构:
1. 华能济南黄台发电有限公司
2. 西安热工研究院有限公司
作者简介:
基金信息:
DOI:
CLC:TK224.9
Published:2012
稿件说明:
移动端阅览
LI Gang1, LI Xixiao1, WEI Tongsheng2, et al. CAUSE ANALYSIS OF HIGH-TEMPERATURE CORROSION OCCURRED ON THE WATER-WALL OF 1025 t/h BOILER AND SOLVING MEASURES THEREOF[J]. Thermal power generation, 2012, 41(2): 53-55.
DOI:
LI Gang1, LI Xixiao1, WEI Tongsheng2, et al. CAUSE ANALYSIS OF HIGH-TEMPERATURE CORROSION OCCURRED ON THE WATER-WALL OF 1025 t/h BOILER AND SOLVING MEASURES THEREOF[J]. Thermal power generation, 2012, 41(2): 53-55.DOI:
CAUSE ANALYSIS OF HIGH-TEMPERATURE CORROSION OCCURRED ON THE WATER-WALL OF 1025 t/h BOILER AND SOLVING MEASURES THEREOF
摘要
针对某发电公司300MW机组1 025t/h锅炉进行的燃烧调整试验表明
水冷壁产生高温腐蚀的主要原因是一次风动量偏低
刚性不足
在壁面处形成了较强的还原性气氛所致。通过增加周界风风量
提高了一次风射流动量
使水冷壁高温腐蚀缓解。此外
优化二次风配风方式可有效改善水冷壁壁面气氛
建议AB/BC/CD/DE二次风挡板按缩腰配风方式运行。对于防止水冷壁大面积的高温腐蚀
贴壁风的作用非常有限。
Abstract
Directing against the problem of high-temperature corrosion occurred on the water-wall of 1 025 t/h boiler for unit no.8 in one power plant
a combustion adjustment test has been carried out.Analysis shows that the main cause is the lower momentum of primary air.Through maintaining certain open-degree of the peripheral air
the momentum of primary air jet has been enhanced
making the high-temperature corrosion occurred on the water-wall to be alleviated.Besides
the distribution mode of secondary air can effectively improve the atmosphere on wall surface of the water-wall
the baffle plates of secondary air AB/BC/CD/DE have to be in operation according to the shrink-waist mode.For high-temperature corrosion in large areas
the influence of air being closed to the wall is very limited.