STUDY ON CONTROL STRATEGY OF AIR-COOLING SYSTEM FOR DIRECT AIR-COOLED UNITS TO SUIT THE AMBIENT TEMPERATURE CHANGE
|更新时间:2025-09-28
|
STUDY ON CONTROL STRATEGY OF AIR-COOLING SYSTEM FOR DIRECT AIR-COOLED UNITS TO SUIT THE AMBIENT TEMPERATURE CHANGE
Thermal Power GenerationVol. 41, Issue 2, Pages: 37-41(2012)
作者机构:
西门子电站自动化有限公司
作者简介:
基金信息:
DOI:
CLC:TM621.6
Published:2012
稿件说明:
移动端阅览
JIN Yunli Siemens Power Plant Automation Co Ltd. STUDY ON CONTROL STRATEGY OF AIR-COOLING SYSTEM FOR DIRECT AIR-COOLED UNITS TO SUIT THE AMBIENT TEMPERATURE CHANGE[J]. Thermal power generation, 2012, 41(2): 37-41.
DOI:
JIN Yunli Siemens Power Plant Automation Co Ltd. STUDY ON CONTROL STRATEGY OF AIR-COOLING SYSTEM FOR DIRECT AIR-COOLED UNITS TO SUIT THE AMBIENT TEMPERATURE CHANGE[J]. Thermal power generation, 2012, 41(2): 37-41.DOI:
STUDY ON CONTROL STRATEGY OF AIR-COOLING SYSTEM FOR DIRECT AIR-COOLED UNITS TO SUIT THE AMBIENT TEMPERATURE CHANGE
The influence of ambient temperature change upon the direct air-cooling system control has been analysed from aspects of the turbine's backpressure control
the fans' electricity consumption
and the anti-freezing control etc.
a control strategy for direct air-cooling system being put forward to suit the ambient temperature change.The control mode based on fan speed is suitable for switching the fan row automatically in summer
but the control mode based on turbine's backpressure is more favorable for switching on the fan row in winter.In summer
the speed-setting controller of fans is suitable to adopt variable parameters
so as to strengthen the adjustment effect as the temperature raises.When the ambient temperature in winter changes from high to low
the anti-freezing protection of downstream fans could adopt sequentially the method of stopping the fans belonging to the row which triggers the protection
stopping fan rows adjacent to the upstream tube bundle block and increasing the set point of turbine' back pressure.When large temperature difference occurred in summer and winter
the fans in isolated and non-isolated streets have to be put into operation separately.In case of the temperature difference being small
the fans in isolated and non-isolated streets have to be put into operation stepwise;under low ambinet temperature in winter
the counter flow fans are suitable to put into operation stepwise.