REASON ANALYSIS AND RELIEF COUNTERMEASURE FOR FREQUENT TEARING OF COMPENSATOR AT THE ENTRANCE OF CONDENSATE WATER PIPELINE
|更新时间:2025-09-28
|
REASON ANALYSIS AND RELIEF COUNTERMEASURE FOR FREQUENT TEARING OF COMPENSATOR AT THE ENTRANCE OF CONDENSATE WATER PIPELINE
Thermal Power GenerationVol. 41, Issue 7, Pages: 112-115(2012)
作者机构:
西安热工研究院有限公司
作者简介:
基金信息:
DOI:
CLC:TM621.72
Published:2012
稿件说明:
移动端阅览
WANG Junmin, CHEN Shengguang, WEI Dawei, et al. REASON ANALYSIS AND RELIEF COUNTERMEASURE FOR FREQUENT TEARING OF COMPENSATOR AT THE ENTRANCE OF CONDENSATE WATER PIPELINE[J]. Thermal power generation, 2012, 41(7): 112-115.
DOI:
WANG Junmin, CHEN Shengguang, WEI Dawei, et al. REASON ANALYSIS AND RELIEF COUNTERMEASURE FOR FREQUENT TEARING OF COMPENSATOR AT THE ENTRANCE OF CONDENSATE WATER PIPELINE[J]. Thermal power generation, 2012, 41(7): 112-115.DOI:
REASON ANALYSIS AND RELIEF COUNTERMEASURE FOR FREQUENT TEARING OF COMPENSATOR AT THE ENTRANCE OF CONDENSATE WATER PIPELINE
摘要
针对某300MW机组凝结水入口管道补偿器频繁发生变形撕裂
多组支吊架严重偏斜
与凝结水管道相连接的热井端口变形明显等问题
建立了凝结水进口管道的受力模型
对管道各吊点的载荷、位移、管道的应力状况及端点推力进行了计算。计算结果表明
管道设计中未考虑介质内压导致的补偿器沿轴线方向伸长是引起上述问题出现的根本原因。对此
建议进行包含补偿器的管道设计时
应采用相应的措施如将7号滑动支架更换为固定支架来"抵消"管道内压推力对补偿器的影响。
Abstract
Compensator in the condensate water pipline of a 300 MW power station unit was continually deformed into cracks.At the same time
supports and hangers of the pipline were draged inclined
and end cap of the heat well connected with the condenate water pipline was also deformed observably.Such a situtation would lead to accident of the power units.To solve this problem
stressing model of the entrance pipline of condensate water was estabilished.Moreover
load on the pipline
its stress and displacement
and also the endpoint thrust were calculated.Results show that
the basic reason for the problems mentioned above is not considering the inner pressure of the medium in pipeline design which will cause the extension of compensator along its axis direction.Suggestion that appropriate measures should be adopted to eliminate the effect of inner pressure of pipeline on the compensator when the pipeline with compensator is designed is given.