CONTROL AND OPTIMIZATION OF CHEMICAL CONDITION IN HIGH pH OXYGEN-ADDING TREATMENT FOR SUPERCRITICAL AIR COOLING UNIT
|更新时间:2025-09-28
|
CONTROL AND OPTIMIZATION OF CHEMICAL CONDITION IN HIGH pH OXYGEN-ADDING TREATMENT FOR SUPERCRITICAL AIR COOLING UNIT
Thermal Power GenerationVol. 41, Issue 9, Pages: 94-98(2012)
作者机构:
河北国华定洲发电有限责任公司
作者简介:
基金信息:
DOI:
CLC:TM621.8
Published:2012
稿件说明:
移动端阅览
DENG Yingchun Hebei Guohua Dingzhou Power Generation Co.Ltd.. CONTROL AND OPTIMIZATION OF CHEMICAL CONDITION IN HIGH pH OXYGEN-ADDING TREATMENT FOR SUPERCRITICAL AIR COOLING UNIT[J]. Thermal power generation, 2012, 41(9): 94-98.
DOI:
DENG Yingchun Hebei Guohua Dingzhou Power Generation Co.Ltd.. CONTROL AND OPTIMIZATION OF CHEMICAL CONDITION IN HIGH pH OXYGEN-ADDING TREATMENT FOR SUPERCRITICAL AIR COOLING UNIT[J]. Thermal power generation, 2012, 41(9): 94-98.DOI:
CONTROL AND OPTIMIZATION OF CHEMICAL CONDITION IN HIGH pH OXYGEN-ADDING TREATMENT FOR SUPERCRITICAL AIR COOLING UNIT
Taking the No.3 and No.4 supercritical 660 MW air cooling units in Guohua Dingzhou Power Generation Co.
Ltd.as objects
the optimization of chemical condition in high pH oxygen-adding treatment for supercritical once-through boiler was summarized from aspects such as influence of CO2 controlling upon the system
the service life of anionic exchange resin under high temperature
the type selection of polishing treatment equipment
and the chemical supervision for preventing corrosion of the air cooled condenser
and so on.After adopting the high pH oxygen-adding treatment mode
the pressure difference of boiler was remarkably reduced
the iron content in condensate maintaining within 10~20 μg/L;the ability of powdered resin filter for desalting and eliminating CO2 is poor;it is better to keep using the mixed bed in summer
and the desuperheating of air cooling condenser by spraying should be strengthed
to lessen the influence of temperature upon the anionic exchange resin.It is better to evaluate the corrosion situation of air coolled condenser via DHACL corrosion index determination method
according to the daily monitoring data of iron content in condensate water.