INFLUENCE OF ENVIRONMENTAL LEEWARD ON THE EXTERNAL FLOW FIELD OF DIRECT AIR-COOLED CONDENSER
Flow field and heat dissipation situation of the condensate unit on a direct air-cooling condenser for a 300 MW unit was simulated.To study the adverse effect of environmental leeward on air-cooled condenser
wind speed at 0 m/s
3 m/s
5 m/s were taken as examples respectively.Results show that
the temperature of air flowing through the condensate unit is higher
inside the A-shape shelf
at the bottom 4 corners
there's strong vortex
and heat dissipation is not obvious.The heat transfer performance will be reduced extremly because of the strong hot air reflow caused by environmental leeward
that is closely related with the flow around effect resulted from tall buildings.The total heat exchange amount was 807 MW
516 MW and 540 MW when the wind speed was as mentioned 0 m/s
3 m/s and 5 m/s
respectively
this indicates that
when the environmental leeward flow rate is not very high
slightly increasing the wind speed can improve the heat transfer performance a bit.