FEED WATER FLOW MEASUREMENT DEVIATION IN ONCE-THROUGH BOILER:REASON ANALYSIS AND SOLUTIONS
Based on analysis of feed water flow measurement deviation in once-through boiler
measurements were taken as follows:adopting independent sampling of feed water flow;using positive pressure side second valve
negative pressure side second valve and balance valve that composed of needle type valve set which can bear pressure more than 40 MPa to replace three valve groups
and to connect to junction of positive pressure side and negative pressure side by screw adding gasket;increasing heat tapes of pipeline.Meanwhile
to measure the feed water flow accurately
it should be ensured that
the sampling devices are arranged reasonably
the sampling pipeline has no leakage
and measurement range of the transmitter is consistent with that of the I/O channel in DCS
furthermore
the DCS data transmission channel is normal.After the treatment
feed water flow deviation values measured at three points were less than 50t/h.
Simulation modelling of power system for supercritical units considering dynamic heat exchange of once-through boiler
PRELIMINARY ANALYSIS OF REQUIREMENTS TO WATER-WALL SYSTEM PERFORMANCE FOR SERVICE OPERATION OF SUPERCRITICAL PRESSURE ONCETHROUGH BOILER OF 600MW UNITS
MATHEMATIC MODEL AND DYNAMIC CHARACTERISTICS OF ONCE-THROUGH BOILER FOR A 300 MW UNIT
EXPLORATION OF FEED-WATER AVT(O) TREATMENT FOR ONCE-THROUGH BOILER OF SUPERCRITICAL 600 MW UNIT
OPTIMIZATION OF PIPE-BLOWING TECHNOLOGY UNDER STABLE PRESSURE FOR SUPERCRITICAL ONCE-THROUGH BOILER
Related Author
XU Fei
HUANG Yihan
LI Jiangpeng
LIU Yifeng
QI Xin
CHEN Lei
HAO Ling
XU Darui
Related Institution
State Grid Ningxia Electric Power Co., Ltd
National Key Laboratory of New Power System Operation and Control, Tsinghua University
Department of Electrical Engineering and Applied Electronic Technology, Tsinghua University
Guangdong Electric Honghai Bay Power Generation Co., Ltd.