ANALYSIS AND COMPARISON OF DRIVEN MODE FOR INDUCED DRAFT FAN IN THERMAL POWER PLANT
|更新时间:2025-09-28
|
ANALYSIS AND COMPARISON OF DRIVEN MODE FOR INDUCED DRAFT FAN IN THERMAL POWER PLANT
Thermal Power GenerationVol. 41, Issue 8, Pages: 12-14(2012)
作者机构:
广东省电力设计研究院
作者简介:
基金信息:
DOI:
CLC:TK223.26
Published:2012
稿件说明:
移动端阅览
TAN Canshen, WU Afeng Guangdong Electric Power Design Institute. ANALYSIS AND COMPARISON OF DRIVEN MODE FOR INDUCED DRAFT FAN IN THERMAL POWER PLANT[J]. Thermal power generation, 2012, 41(8): 12-14.
DOI:
TAN Canshen, WU Afeng Guangdong Electric Power Design Institute. ANALYSIS AND COMPARISON OF DRIVEN MODE FOR INDUCED DRAFT FAN IN THERMAL POWER PLANT[J]. Thermal power generation, 2012, 41(8): 12-14.DOI:
ANALYSIS AND COMPARISON OF DRIVEN MODE FOR INDUCED DRAFT FAN IN THERMAL POWER PLANT
ID fans in operating power plants are always driven by electromotor
while the increasing capacity of the electromotor will cause higher service power consumption rate.So
this paper compares the technical and economic difference between different driven ways for ID fans(by steam turbine or electromotor)
and also discusses the economical efficiency and energy consumption of the steam turbine driven ID fans.Newly built generator units will have lower initial investment and easier operation maintenance by adopting the electromotor to drive ID fans.However
using steam turbine to drive can decrease the service power consumption rate
and avoid the impact of motor starting current on auxiliary power system.For the retrofitted units which change electromotor driving into steam turbine driving
it should be checked whether the parameters of following systems can satisfy the turbine driven requirements
such as boiler
main steam turbine
condensate system
extraction steam system
auxiliary steam system and circulating water system etc.Steam turbine driven ID fans adopted on either newly built or retrofitted units both have certain economic advantages