Selection of steam-driven induced draft fan considering piping thermal efficiency
|更新时间:2025-09-28
|
Selection of steam-driven induced draft fan considering piping thermal efficiency
Thermal Power GenerationVol. 42, Issue 1, Pages: 5-8(2013)
作者机构:
上海电力学院能源与环境工程学院
作者简介:
基金信息:
DOI:
CLC:TM621
Published:2013
稿件说明:
移动端阅览
JIN Rong, SHI Qiguang, YANG Yanling, et al. Selection of steam-driven induced draft fan considering piping thermal efficiency[J]. Thermal power generation, 2013, 42(1): 5-8.
DOI:
JIN Rong, SHI Qiguang, YANG Yanling, et al. Selection of steam-driven induced draft fan considering piping thermal efficiency[J]. Thermal power generation, 2013, 42(1): 5-8.DOI:
Selection of steam-driven induced draft fan considering piping thermal efficiency
摘要
以亚临界600MW机组引风机由电动改汽动驱动为例
分析了汽动引风机5种不同汽源方案的热经济性。结果表明
采用主汽轮机(主机)回热抽汽驱动引风机
机组绝对电效率下降
而厂用电率下降幅度较大
因此全厂供电煤耗率下降。当不考虑管道效率的变化时
以方案Ⅲ为例
供电标准煤耗的下降值由1.556g/(kW.h)增至2.026g/(kW.h)
即过高地评估了系统改进后机组的经济性。采用方案Ⅲ并考虑管道效率的变化
全厂供电标准煤耗下降1.556g/(kW.h)
按全年运行7 000h计算可节约标准煤6 535.2t
Ⅲ优于其它4个方案。
Abstract
Based on the transformation that the driven method of the induced draft fan(IDF) for a subcritical 600 MW unit was changed from motor driven to steam driven
the thermal economy of five schemes for steam-driven IDF with different steam sources were analyzed.The results showed that
using the regenerative steam to drive the IDF would reduce the absolute electric efficiency
but the auxiliary power consumption rate decreased greater
so the coal consumption rate of the power supply for the whole plant was reduced.If not considering the piping efficiency's variation
taking scheme Ⅲ as an example
the drop amount of the standard coal consumption was increased from 1.556 g/(kW·h) to 2.026 g/(kW·h)
namely the economic benefit of this modification(motor-driven to steam-driven) was over estimated.For scheme Ⅲ with considering the piping efficiency's variation
the standard coal consumption rate for the whole plant was reduced by about 1.556 g/(kW·h).Assuming that the unit runs for 7 000 h per year
this scheme can totally save standard coal of 6 535.2 t.Scheme Ⅲ is superior to other four schemes.