Wall temperature variation of high temperature heating surface in boiler of an ultra supercritical 1000 MW unit
|更新时间:2025-09-28
|
Wall temperature variation of high temperature heating surface in boiler of an ultra supercritical 1000 MW unit
Thermal Power GenerationVol. 42, Issue 2, Pages: 117-120(2013)
作者机构:
国电浙江北仑第一发电有限公司
作者简介:
基金信息:
DOI:
CLC:TK229.2
Published:2013
稿件说明:
移动端阅览
ZHOU Jiang, YU Mingfang, YANG Zhuojun Guodian Zhejiang Beilun No.1 Power Generation Co.. Wall temperature variation of high temperature heating surface in boiler of an ultra supercritical 1000 MW unit[J]. Thermal power generation, 2013, 42(2): 117-120.
DOI:
ZHOU Jiang, YU Mingfang, YANG Zhuojun Guodian Zhejiang Beilun No.1 Power Generation Co.. Wall temperature variation of high temperature heating surface in boiler of an ultra supercritical 1000 MW unit[J]. Thermal power generation, 2013, 42(2): 117-120.DOI:
Wall temperature variation of high temperature heating surface in boiler of an ultra supercritical 1000 MW unit
outlet wall temperature of heating surface and measuring points location on the boiler inner wall temperature variation
the real-time data of boiler operation and inner wall temperature in high-temperature heating surface of an ultra supercritical unit were measured.Wall temperature variation curves of the high-temperature reheater and high-temperature superheater were obtained.The results showed that
the outlet temperature of heating surface can not correctly reflect the actual furnace wall temperature.The variation of wall temperature was consistent with that of the uint load.Temperature at front wall of the high-temperature superheater decreased with an increase in unit load
while that at the back wall agreed well with the unit load.