Thermal Power GenerationVol. 41, Issue 12, Pages: 78-80(2012)
作者机构:
1. 西安热工研究院有限公司
2. 神华亿利能源有限责任公司
作者简介:
基金信息:
DOI:
CLC:TK223.32
Published:2012
稿件说明:
移动端阅览
ZHANG Zhibo1, YAO Bingyin1, MA Jianmin1, et al. TUBE BURST OF PLATEN SUPERHEATER ON A CIRCULATING FLUIDIZED BED BOILER:REASON ANALYSIS AND SOLVING MEASURES[J]. Thermal power generation, 2012, 41(12): 78-80.
DOI:
ZHANG Zhibo1, YAO Bingyin1, MA Jianmin1, et al. TUBE BURST OF PLATEN SUPERHEATER ON A CIRCULATING FLUIDIZED BED BOILER:REASON ANALYSIS AND SOLVING MEASURES[J]. Thermal power generation, 2012, 41(12): 78-80.DOI:
TUBE BURST OF PLATEN SUPERHEATER ON A CIRCULATING FLUIDIZED BED BOILER:REASON ANALYSIS AND SOLVING MEASURES
摘要
某循环流化床(CFB)锅炉屏式过热器发生爆管
通过对爆管管样进行金相组织检验、化学成分分析、机械性能测试等
认为爆管是由长期超温运行所致。对此
采取减少屏式过热器的换热面积
将部分管子割除短接等措施后
屏式过热器冷段出口壁温为455℃左右
热段出口壁温为488℃左右
均在合理范围
超温问题得到了明显改善。
Abstract
Tube burst occurred on platen superheater of a circulating fluidized bed boiler(CFB).Based on series of tests such as microstructure examination
chemical composition analysis and mechanical property test
long time over-temperature operation was considered as the main reason.Thus
heating surface of the platen superheater was changed into water cooling evaporate panel
to reduce the heat exchange surface
and increase the flow speed of medium inside the pipe.Furthermore
part of the superheater pipes were cut
and the coverage area of refractory were enlarged
too.Results show that
after the improvement
the outlet wall temperature of primary platen superheater is about 455 ℃
and the one for final platen superheater is about 488 ℃