Influence of secondary air declivitous angle on flow characteristics and coal combustion of a down-fired boiler
|更新时间:2025-09-28
|
Influence of secondary air declivitous angle on flow characteristics and coal combustion of a down-fired boiler
Thermal Power GenerationVol. 42, Issue 1, Pages: 56-58(2013)
作者机构:
贵州电力试验研究院
作者简介:
基金信息:
DOI:
CLC:TK227
Published:2013
稿件说明:
移动端阅览
SHI Jian, CHEN Yuzhong, HOU Yubo Guizhou Electric Power Test and Research Institute. Influence of secondary air declivitous angle on flow characteristics and coal combustion of a down-fired boiler[J]. Thermal power generation, 2013, 42(1): 56-58.
DOI:
SHI Jian, CHEN Yuzhong, HOU Yubo Guizhou Electric Power Test and Research Institute. Influence of secondary air declivitous angle on flow characteristics and coal combustion of a down-fired boiler[J]. Thermal power generation, 2013, 42(1): 56-58.DOI:
Influence of secondary air declivitous angle on flow characteristics and coal combustion of a down-fired boiler
摘要
通过在FW型W火焰锅炉F层风箱内加装二次风下倾角度调节装置
实现了F层二次风下倾角度的自由调节
以适应锅炉运行工况的变化
改善炉内燃烧过程
提高锅炉燃烧效率。试验结果表明
一次风气流的下行深度随调节挡板角度的增加而增加
当挡板调至45°时
炉内流场组织最佳;改造后锅炉飞灰含碳量由10%左右降至4.4%左右
锅炉减温水量由100t/h以上降至65t/h左右
锅炉效率由86.95%提高到90.11%。
Abstract
A secondary air declivitous angle regulating device installed at F layer wind box of a FW(Foster Wheeler) down-fired boiler was designed
to realize freedom regulation of the secondary air declivitous angle
and to adapt to the change of operation conditions
thus to improve the combustion performance and increase the boiler efficiency.The experimental results showed that
the down flow depth of the primary air increased with the declivitous angle.The best flow field was achieved when the declivitous angle was set at 45°.After the improvement
the fly ash carbon content decreased from 10% to 4.4%(by more than 5%);the desuperheater spray quantity fell from up to 100 t/h to 65 t/h;the boiler efficiency increased from 86.95% to 90.11%.