Case analysis of ultrafiltration membrane fouling in a power plant and the cleaning method
|更新时间:2025-09-28
|
Case analysis of ultrafiltration membrane fouling in a power plant and the cleaning method
Thermal Power GenerationVol. 42, Issue 9, Pages: 141-143(2013)
作者机构:
西安热工研究院有限公司
作者简介:
基金信息:
DOI:
CLC:TQ085.4
Published:2013
稿件说明:
移动端阅览
LI Yajuan, XU Zhen, YIN Ping, et al. Case analysis of ultrafiltration membrane fouling in a power plant and the cleaning method[J]. Thermal power generation, 2013, 42(9): 141-143.
DOI:
LI Yajuan, XU Zhen, YIN Ping, et al. Case analysis of ultrafiltration membrane fouling in a power plant and the cleaning method[J]. Thermal power generation, 2013, 42(9): 141-143.DOI:
Case analysis of ultrafiltration membrane fouling in a power plant and the cleaning method
摘要
某超滤系统运行中出现产水量显著下降
对超滤膜丝进行电镜和能谱分析发现
其主要是由铁、锰胶体以及无机钙垢造成超滤膜的污堵所致
对此
采用盐酸、硫酸、柠檬酸、草酸溶液对膜丝进行静态浸泡试验。结果表明
草酸对铁锰胶体的清洗效果最好
实际清洗后
跨膜压差和产水量基本恢复至初始状态。
Abstract
The water yield dropped significantly during operation of an ultrafiltration system.The electron microscope analysis and energy spectrum analysis indicated the iron-manganese colloid and calcium scale were the main contaminants.Thus
the hydrochloric acid
sulfuric acid
oxalic acid and citric acid were used as the cleaning solvent to conduct static immersion test.The results showed that citric acid had the best cleaning effect on iron-manganese colloid.After cleaning
the transmembrane pressure difference and water yield recovered to the initial values.