Rule based primary frequency regulation algorithm : design and implementation
|更新时间:2025-09-28
|
Rule based primary frequency regulation algorithm : design and implementation
Thermal Power GenerationVol. 42, Issue 8, Pages: 131-134(2013)
作者机构:
1. 辽宁省电力有限公司电力科学研究院
2. 国电电力大连开发区电厂
作者简介:
基金信息:
DOI:
CLC:TM76
Published:2013
稿件说明:
移动端阅览
HAO Xin1, Wang Yinghui 1, Yu Xueli 2 1.Electric Power Science Institute. Rule based primary frequency regulation algorithm : design and implementation[J]. Thermal power generation, 2013, 42(8): 131-134.
DOI:
HAO Xin1, Wang Yinghui 1, Yu Xueli 2 1.Electric Power Science Institute. Rule based primary frequency regulation algorithm : design and implementation[J]. Thermal power generation, 2013, 42(8): 131-134.DOI:
Rule based primary frequency regulation algorithm : design and implementation
The calculation method for primary frequency regulation index in Liaoning power grid was investigated.Rule based primary frequency regulation optimal control algorithm and logic design scheme were put forward.For digital electro-hydraulic(DEH)system and unit coordinated control(UCC)system
several functions were added
such as dynamic correction for unequal rate function gain
nonlinear correction for flow instruction of primary frequency feedforward component
and dynamic separation of main steam pressure deviation in turbine main control.The optimal debug methods for primary frequency regulation using the synchronized phasor measurement unit(PMU)data from power dispatching center were summarized.By this control algorithm
the simulated test and application of primary frequency regulation under unit full load condition was conducted.The results showed that the unit load track was sensitive
and the load regulation amplitude deviationβ3was 16.9%
which dramatically satisfied the requirement(lower than 25%)of primary frequency regulation index.