Simulation study on coordinated control system of subcritical 600 MW unit
Combined with the operation parameters of Wu Jing Second Power Plant
the mathematic model for coordinated control system in a subcritical 600 MW unit was established
on the basis of the coordinated control model.By Simulink software
simulation on this model was conducted and the results were compared with the unit operation data.With a constant opening degree of regulating valve
when the coal feed quantity was changed
the maximum error between the simulated value and actual value of the main steam pressure was below 0.3 MPa
and that of the turbine power was less than 3 MW.When the coal feed quantity was kept constant and the opening degree of regulating valve varied
the maximum error between the simulated value and actual value of the main steam pressure was within 0.2 MPa
and that of the turbine power was below 4.5 MW.The small dynamic error between the model and the unit operation demonstrated the feasibility of the above mathematic model for coordinated control system.Based on this model
the unit coordinated control system was improved
by direct energy balance(DEB) method.The simulation results showed that
the improved unit coordinated control system had high response speed and strong anti-interference
and can control the fluctuation of main steam pressure well.