Fault analysis and treatment for shaft system vibration of a 1000 MW unit during its debugging period
|更新时间:2025-09-28
|
Fault analysis and treatment for shaft system vibration of a 1000 MW unit during its debugging period
Thermal Power GenerationVol. 42, Issue 2, Pages: 89-91(2013)
作者机构:
1. 西安热工研究院有限公司
2. 华能海门电厂
作者简介:
基金信息:
DOI:
CLC:TM621
Published:2013
稿件说明:
移动端阅览
WANG Yanbo1, ZHANG Weijiang2, YANG Qing1 1.Xi'an Thermal Power Research Institute Co.Ltd.. Fault analysis and treatment for shaft system vibration of a 1000 MW unit during its debugging period[J]. Thermal power generation, 2013, 42(2): 89-91.
DOI:
WANG Yanbo1, ZHANG Weijiang2, YANG Qing1 1.Xi'an Thermal Power Research Institute Co.Ltd.. Fault analysis and treatment for shaft system vibration of a 1000 MW unit during its debugging period[J]. Thermal power generation, 2013, 42(2): 89-91.DOI:
Fault analysis and treatment for shaft system vibration of a 1000 MW unit during its debugging period
For the No.3 supercritical 1 000 MW unit in Huaneng Haimen Power Plant
its high pressure rotor had a rotor friction between dynamic and static parts during high speed warm-up period
after continuous turning gear for 2 hours
the fault was eliminated.Because the shaft sealing steam temperature was about 20 ℃ lower than the normal value when the turbine ran under large load for the first time
the low pressure B rotor had the same fault
and the vibration was eliminated through improving the shaft sealing steam temperature and keeping it at the normal level.Under rated load condition
the shaft vibration amplitudes of measuring point 7Y
9Y
and 10Y reached the alarm value
respectively
through conducting field high speed dynamic balancing for the low pressure B rotor and the generator rotor