Thermal economic analysis on an ultra supercritical unit with second reheat cycle
|更新时间:2025-09-28
|
Thermal economic analysis on an ultra supercritical unit with second reheat cycle
Thermal Power GenerationVol. 42, Issue 9, Pages: 7-9(2013)
作者机构:
1. 长安大学环境科学与工程学院
2. 西安热工研究院有限公司
作者简介:
基金信息:
DOI:
CLC:TM306
Published:2013
稿件说明:
移动端阅览
GU Yaxiu, WANG Shengpeng, YANG Shoumin, et al. Thermal economic analysis on an ultra supercritical unit with second reheat cycle[J]. Thermal power generation, 2013, 42(9): 7-9.
DOI:
GU Yaxiu, WANG Shengpeng, YANG Shoumin, et al. Thermal economic analysis on an ultra supercritical unit with second reheat cycle[J]. Thermal power generation, 2013, 42(9): 7-9.DOI:
Thermal economic analysis on an ultra supercritical unit with second reheat cycle
On the basis of keeping the main steam pressure and temperature and reheat steam temperature of the unit with single reheat cycle constant
applying second reheat cycle can reduce the heat consumption rate and enhance the unit efficiency.Taking an ultra supercritical 1 000MW unit with double reheat cycles and steam parameter of 26.25MPa/600℃/600℃/600℃as the example
comparison of the thermal economic indices of unit running with single reheat and double reheat was conducted.The results showed that
under 1 000 MW unit load condition
compared with the turbine running with single reheat
the heat consumption rate of that running with double reheat decreased by 1.26%
about 92kJ/(kW·h)lower;the coal consumption for power supply decreased by 3.47g/(kW·h)and the unit net efficiency increased by 0.57%.