Optimization of feedforward control strategy for coordinated control system with indirect energy balance
|更新时间:2025-09-28
|
Optimization of feedforward control strategy for coordinated control system with indirect energy balance
Thermal Power GenerationVol. 42, Issue 4, Pages: 53-56(2013)
作者机构:
华北电力科学研究院西安公司
作者简介:
基金信息:
DOI:
CLC:TK323
Published:2013
稿件说明:
移动端阅览
WANG Li North China Electric Power Research Institute(Xi'an) Co.. Optimization of feedforward control strategy for coordinated control system with indirect energy balance[J]. Thermal power generation, 2013, 42(4): 53-56.
DOI:
WANG Li North China Electric Power Research Institute(Xi'an) Co.. Optimization of feedforward control strategy for coordinated control system with indirect energy balance[J]. Thermal power generation, 2013, 42(4): 53-56.DOI:
Optimization of feedforward control strategy for coordinated control system with indirect energy balance
摘要
对于非线性较强的主蒸汽压力和机组负荷
单纯采用机炉主控制系统的间接能量平衡(IEB)协调控制策略
难以在机组变负荷工况下取得较好的控制品质。对此
基于传统的IEB协调控制系统和汽包锅炉动态模型
设计了适应于单元机组特性的前馈控制策略
并分析了该前馈控制的特点
给出了控制参数的在线整定方法。该方法在机组的负荷响应试验过程中
使主蒸汽压力最大动态偏差0.35MPa
表明优化后的IEB协调控制系统具有较好的动态调节品质。
Abstract
For the main steam pressure and unit load with strong nonlinearity
indirect energy balance(IEB) coordinated control which simply depending on the boiler-turbine master controller can hardly obtain good control quality under variable load conditions.On the basis of the conventional IEB coordinated control system and dynamic model of drum boiler
a feedforward control strategy which was suitable to the unit performance was designed.The features of this feedforward control was analyzed
and the online setting method for the control parameters was put forward.During the unit load response test
the maximum dynamic deviation of the main steam pressure was below 0.35 MPa
indicating the optimized IEB coordinated control system had good dynamic regulating performance.