Uncertainty of performance test for mixed indirect air cooling system
|更新时间:2025-09-28
|
Uncertainty of performance test for mixed indirect air cooling system
Thermal Power GenerationVol. 42, Issue 7, Pages: 22-25(2013)
作者机构:
国电科学技术研究院
作者简介:
基金信息:
DOI:
CLC:TM621
Published:2013
稿件说明:
移动端阅览
YANG Wenzheng, HUANG Qilong, DAI Weibao Guodian Science and Technology Research Institute. Uncertainty of performance test for mixed indirect air cooling system[J]. Thermal power generation, 2013, 42(7): 22-25.
DOI:
YANG Wenzheng, HUANG Qilong, DAI Weibao Guodian Science and Technology Research Institute. Uncertainty of performance test for mixed indirect air cooling system[J]. Thermal power generation, 2013, 42(7): 22-25.DOI:
Uncertainty of performance test for mixed indirect air cooling system
Combining with the performance test standards for air cooling system
the universal formula of the uncertainty calculation for thermal performance guarantee value by general characteristic curve method was derived.By this formula
the performance tests uncertainty for a mixed indirect air cooling system was determined as 0.032 5.It can be seen from the uncertainty distribution that
such factors as water temperature at inlet/outlet of the tower
circulating cooling water flow and pressure in condenser were main parameters affecting the tests uncertainty.The uncertainty was evaluated from several aspects
like measuring point number
instrument accuracy
parameter fluctuation range and so on.It indicated that the water temperature at inlet/outlet of the tower should be measured at multiple points;the uncertainty of the test results can be reduced by about 0.005 3by enhancing the accuracy of flow measurement instrument for circulating water of 1%;selecting appropriate test time and controlling the measuring parameters fluctuation be within a reasonable range can effectively reduce the uncertainty of the test results.