Effect of environmental temperature on cogeneration units and the countermeasures
|更新时间:2025-09-28
|
Effect of environmental temperature on cogeneration units and the countermeasures
Thermal Power GenerationVol. 42, Issue 5, Pages: 11-14(2013)
作者机构:
华北电力大学能源动力与机械工程学院
作者简介:
基金信息:
DOI:
CLC:TM611
Published:2013
稿件说明:
移动端阅览
GUO Minchen, FAN Xue, FU Li, et al. Effect of environmental temperature on cogeneration units and the countermeasures[J]. Thermal power generation, 2013, 42(5): 11-14.
DOI:
GUO Minchen, FAN Xue, FU Li, et al. Effect of environmental temperature on cogeneration units and the countermeasures[J]. Thermal power generation, 2013, 42(5): 11-14.DOI:
Effect of environmental temperature on cogeneration units and the countermeasures
摘要
针对热电联产机组冬季存在空冷凝汽器冻结和供热抽汽参数调节滞后的问题
结合某4×220MW直接空冷热电联产机组进行了热力计算
得出不同环境温度对应的凝汽器最小蒸汽流量和供热抽汽流量
并利用origin软件绘制出相应的性能曲线。通过分析发现:随着环境温度升高
流入凝汽器的蒸汽量逐渐降低
并且蒸汽量的变化率逐渐减小;当环境温度低于零下5℃时
基本热网加热器已经达到最大热负荷
需要启动尖峰热网加热器以满足热用户的需求;当环境温度低于零下6℃时
所需总蒸汽流量已经超过最大主蒸汽流量
此时需要加大燃料投入
增大主蒸汽流量
或关闭部分空冷凝汽器单元
减小发电量。该方法能够准确计算不同温度对应的热电比例
及时调整发电和供热参数
实现能量的合理利用。
Abstract
Against such problems as frozen in air cooled condenser and lag in heat supply extraction parameter adjustment that occurred on cogeneration units in winter
a model was established to conduct thermal dynamic calculation
combining with a 4×220 MW direct air cooled cogeneration uni.The minimum condenser steam flow and heat supply extraction flow under different environmental temperatures were obtained
and the origin software was employed to draw the corresponding performance curves.The results showed that
with an increase in the environmental temperature
the steam amount required by condenser reduced and the variation rate of the steam flow decreased gradually.When the environmental temperature was lower than-5 ℃
the basic heater had reached the maximum heating load
peak-load heater should be started to satisfy the heat users.When the environmental temperature was below-6 ℃
the required total steam amount had exceeded the maximum steam amount
so fuel input should be increased to improve the main steam amount or part of the condenser units should be shut down to reduce power generation.This method can calculate the heat/electricity ratio at different environmental temperatures correctly and regulate the parameters of power generation and heat supply timely to realize the reasonable utilization of energy.