Optimization of backpressure control strategy for a 600MW supercritical direct air-cooled unit
|更新时间:2025-09-28
|
Optimization of backpressure control strategy for a 600MW supercritical direct air-cooled unit
Thermal Power GenerationVol. 42, Issue 7, Pages: 18-21(2013)
作者机构:
1. 江西省电力科学研究院
2. 南昌工程学院机械与电气学院
作者简介:
基金信息:
DOI:
CLC:TM621
Published:2013
稿件说明:
移动端阅览
HE Jun 1, LIU Baoling 2, YAN Bo 1 1.Department of Auto Control. Optimization of backpressure control strategy for a 600MW supercritical direct air-cooled unit[J]. Thermal power generation, 2013, 42(7): 18-21.
DOI:
HE Jun 1, LIU Baoling 2, YAN Bo 1 1.Department of Auto Control. Optimization of backpressure control strategy for a 600MW supercritical direct air-cooled unit[J]. Thermal power generation, 2013, 42(7): 18-21.DOI:
Optimization of backpressure control strategy for a 600MW supercritical direct air-cooled unit
摘要
针对山西河曲电厂超临界600MW直接空冷机组汽轮机背压控制超调大、难以稳定等问题
对空冷系统防冻保护、空冷风机切步等控制逻辑进行了增加抗干扰回路、背压控制参数自适应等优化。优化后
从汽轮机旁路阀开启到机组带负荷且投入防冻保护功能的起机过程中背压最大偏差小于0.8kPa
实现了空冷岛全过程自动控制
背压控制稳定
保证了空冷机组运行的安全性和稳定性。
Abstract
Aiming at soling such problems as large overshoot and unstable which existed in backpressure control system of air-cooled island for 600 MW direct air-cooled unit of Hequ Power Plant in Shanxi province
improvement measures including adding anti-interference circuit and adaptive adjustment parameters have been proposed to optimize the control logic of anti-freeze protection and cut step operation of air cooling fan.After the optimization
the maximum deviation of the backpressure was below 0.8kPa in start up process of the unit.It has been proved that the proposed measures have ensured the stability of the backpressure control and realized the whole process automation of air-cooling system
which to some extend have enhanced the economy
stability and safety during the operation of above-mentioned air-cooling unit.
ESTABLISHMENT AND ANALYSIS OF DYNAMIC MATHEMATICAL MODEL FOR EMULATION SYSTEM OF SUPERCRITICAL 600 MW ONCE-THROUGH BOILER UNIT
FEATURES OF COMMISSION DEBUGGING FOR HOME-MADE SUPERCRITICAL UNITS AS WELL AS ANALYSIS AND TREATMENT OF MAIN PROBLEMS
ANALYSIS OF VIBRATION PROBLEM FOR HOME - MADE 600 MW SUPERCRITICAL TURBO - GENERATOR SET AND TREATMENT THEREOF
FEATURES OF SHAFTING SYSTEM FOR THE FIRST SUPERCRITICAL 600MW TURBO-GENERATOR SET MANUFACTURED BY BAPE CORPORATION,AS WELL AS VIBRATION ANALYSIS AND DISPOSAL THEREOF