Measurment and empirical correlation of heat transfer coefficient in external heat exchanger of a CFB boiler
|更新时间:2025-09-28
|
Measurment and empirical correlation of heat transfer coefficient in external heat exchanger of a CFB boiler
Thermal Power GenerationVol. 43, Issue 1, Pages: 115-117(2014)
作者机构:
中国华能集团清洁能源技术研究院有限公司
作者简介:
基金信息:
DOI:
CLC:TK229.66;TK31
Published:2014
稿件说明:
移动端阅览
SUN Xianbin, SHI Zhenghai, JIN Senwang, et al. Measurment and empirical correlation of heat transfer coefficient in external heat exchanger of a CFB boiler[J]. Thermal power generation, 2014, 43(1): 115-117.
DOI:
SUN Xianbin, SHI Zhenghai, JIN Senwang, et al. Measurment and empirical correlation of heat transfer coefficient in external heat exchanger of a CFB boiler[J]. Thermal power generation, 2014, 43(1): 115-117.DOI:
Measurment and empirical correlation of heat transfer coefficient in external heat exchanger of a CFB boiler
The heat transfer coefficient of external heat exchanger is key parameters for designing large-capacity circulating fluidized bed(CFB)boiler.In order to measure heat transfer coefficient in external heat exchanger of the CFB boiler
the measurement of heat transfer coefficient in the external heat exchanger was performed on a hot test facility with heating power of 4 MW.The effect of bed temperature and fluidized velocity on heat transfer characteristics was investigated. Through regression analysis on the test data
the correlation formula of heat transfer coefficient in external heat exchanger was obtained.The error between the heat transfer coefficient's calculated value and measured value was less than 14%
indicating the correlation equation has high calculation accuracy and can be applied in design calculation for CFB boilers.