New calorific value calibration method for coordinated control of supercritical air-cooling units:study and application
|更新时间:2025-09-28
|
New calorific value calibration method for coordinated control of supercritical air-cooling units:study and application
Thermal Power GenerationVol. 43, Issue 1, Pages: 46-51(2014)
作者机构:
1. 保定电力职业技术学院动力工程系
2. 神华国华定洲发电有限责任公司
作者简介:
基金信息:
DOI:
CLC:TK323
Published:2014
稿件说明:
移动端阅览
NI Min, WEI Xiangguo, ZHANG Mingfa. New calorific value calibration method for coordinated control of supercritical air-cooling units:study and application[J]. Thermal power generation, 2014, 43(1): 46-51.
DOI:
NI Min, WEI Xiangguo, ZHANG Mingfa. New calorific value calibration method for coordinated control of supercritical air-cooling units:study and application[J]. Thermal power generation, 2014, 43(1): 46-51.DOI:
New calorific value calibration method for coordinated control of supercritical air-cooling units:study and application
For the 2×660 MW air cooling units of Shenhua Guohua Dingzhou Power Generation Plant
the variations of turbine back pressure and fuel calorific value usually affect much on the unit efficiency
in variable loads and different environmental conditions.Using the conventional calorific value correction method will accumulate and increase the deviation of the coordinated control parameters gradually
resulting in decrease in unit load response speed and operation stability.Thus
on the basis of direct command balance principle
a new calorific value calibration method was put forward.Comprehensively considering such factors as the effects of fuel calorific value and turbine back pressure on the unit efficiency
and efficiency difference of unit with differentloads under the same external environmental condition
this new method performed relative reasonable correction on the relationship of the boiler fuel quantity instructions
to ensure the control quality of the coordinated control system under different working conditions.After the new calorific value calibration method was employed
the unit load dropped from 600MW to 300MW
the turbine back pressure dropped from 8.9kPa to 7.8kPa
and the integral output of the boiler master control pressure regulator dropped from +0.2to-1.2(affected by the mill shutdown). After the load variation
the maximum deviation of main steam pressure was +0.2 MPa and-0.4MPa
which was reasonable;the unit load increased from 445 MW to 495 MW
with the load variation rate of 2%/min
the load response time of 40s
load dynamic deviation less than 0.5%
the maximum dynamic deviation of main steam pressure of-0.2MPa